Table 9 continued: Group 11: Reference Select
1104
REF1 MIN
Sets the minimum for external reference 1 .
• The minimum analog input signal (as a percent of the full signal in volts or amperes) corresponds to REF1 MIN in Hz/rpm .
• Parameter 1301 MINIMUM AI1 or 1304 MINIMUM AI2 sets the minimum analog input signal . Does not apply to Daikin MicroTech III applications .
• These parameters (reference and analog min . and max . settings) provide scale and offset adjustment for the reference .
1105
REF1 MAX
Sets the maximum for external reference 1 .
• The maximum analog input signal (as a percent of full the signal in volts or amperes) corresponds to REF1 MAX in Hz/rpm .
• Parameter 1302 MAXIMUM AI1 or 1305 MAXIMUM AI2 sets the maximum analog input signal . Does not apply to Daikin MicroTech III applications .
1106
REF2 SELECT
Selects the signal source for external reference REF2 .
0...17 – Same as for parameter 1103 REF1 SELECT .
19 = PID1OUT – The reference is taken from the PID1 output . See Group 40: PROCESS PID SET 1 and Group 41: PROCESS PID SET 2 . Does not apply to
Daikin MicroTech III applications .
20...21 – Same as for parameter 1103 REF1 SELECT
www .DaikinApplied .com
23
P
araMeTers
0 .0...500 .0
Hz /
0 .1 Hz /
0 .0 Hz /
0...30000
1 rpm
0 rpm
rpm
0 .0...500 .0
60 .0 Hz
Hz /
0 .1 Hz /
(US) / 1800
0...30000
1 rpm
rpm (US)
rpm
0...17,
19
1
19...21
(PID1OUT)
OM 1191 • MD5 VFD