Table 10 continued: Group 12: Constant Speeds
Code
Description
-7 = DI1,2(INV) – Selects one of three Constant Speeds (1...3) using DI1 and DI2 .
• Inverse operation uses two digital inputs, as defined below (0 = DI de-activated, 1 = DI activated):
DI1
DI2
Function
1
1
No constant speed
0
1
Constant speed 1 (1202)
1
0
Constant speed 2 (1203)
0
0
Constant speed 3 (1204)
-8 = DI2,3(INV) – Selects one of three Constant Speeds (1...3) using DI2 and DI3 .
• See above (DI1,2(INV)) for code .
-9 = DI3,4(INV) – Selects one of three Constant Speeds (1...3) using DI3 and DI4 .
• See above (DI1,2(INV)) for code .
-10 = DI4,5(INV) – Selects one of three Constant Speeds (1...3) using DI4 and DI5 .
• See above (DI1,2(INV)) for code .
-11 = DI5,6(INV) – Selects one of three Constant Speeds (1...3) using DI5 and DI6 .
• See above (DI1,2(INV)) for code .
-12 = DI1,2,3(INV) – Selects one of seven Constant Speeds (1...7) using DI1, DI2 and DI3 .
• Inverse operation uses three digital inputs, as defined below (0 = DI de-activated, 1 = DI activated):
DI1
DI2
DI3
1
1
0
1
1
0
0
0
-13 = DI3,4,5(INV) – Selects one of seven Constant Speeds (1...7) using DI3, DI4 and DI5 .
• See above (DI1,2,3(INV)) for code .
-14 = DI4,5,6(INV) – Selects one of seven Constant Speeds (1...7) using DI4, DI5 and DI6 .
• See above (DI1,2,3(INV)) for code .
1209
TIMED MODE SEL
Defines timed function activated constant speed mode. Timed function can be used to change between the external reference and constant speeds when
parameter 1201 CONST SPEED SEL = 15...18 (TIMED FUNC 1...4) or 19 (TIMED FUN1&2) .
1 = EXT/CS1/2/3
• If parameter 1201 = 15...18 (TIMED FUNC 1...4), selects an external speed when this timed function (1...4) is not active and selects Constant speed 1
when it is active .
TIMED FUNCTION 1...4
0
1
• If parameter 1201 = 19 (TIMED FUN1&2), selects an external speed when neither timed function is active, selects Constant speed 1 when only Timed
function 1 is active, selects Constant speed 2 when only Timed function 2 is active and selects Constant speed 3 when both Timed functions 1 and 2
are active .
TIMED FUNCTION 1
0
1
0
1
2 = CS1/2/3/4
• If parameter 1201 = 15...18 (TIMED FUNC 1...4), selects Constant speed 1 when this timed function (1...4) is not active and selects Constant speed 2
when it is active .
TIMED FUNCTION 1...4
0
1
• If parameter 1201 = 19 (TIMED FUN1&2), selects Constant speed 1 when neither timed function is active, selects Constant speed 2 when only Timed
function 1 is active, selects Constant speed 3 when only Timed function 2 is active and selects Constant speed 4 when both Timed functions 1 and 2
are active .
TIMED FUNCTION 1
0
1
0
1
www .DaikinApplied .com
Function
1
No constant speed
1
Constant speed 1 (1202)
1
Constant speed 2 (1203)
1
Constant speed 3 (1204)
Function
External reference
Constant speed 1 (1202)
TIMED FUNCTION 2
Function
0
External reference
0
Constant speed 1 (1202)
1
Constant speed 2 (1203)
1
Constant speed 3 (1204)
Function
Constant speed 1 (1202)
Constant speed 2 (1203)
TIMED FUNCTION 2
Function
0
Constant speed 1 (1202)
0
Constant speed 2 (1203)
1
Constant speed 3 (1204)
1
Constant speed 4 (1205)
25
P
araMeTers
Range
Resolution
Default
2
1, 2
1
(CS1/2/3/4)
OM 1191 • MD5 VFD