Diagnostics – EFB

Fault Queue for Drive Diagnostics

For general MD5 diagnostics information, see
page
74 . The three most recent MD5 faults are reported to
the fieldbus as defined below. For specific MD5 fault codes,
see
Table 55: Fault Listing on page
Table 35: MD5 Faults
Drive Parameter
0401
0412
Previous Fault 1
0413
Previous Fault 2

Serial Communication Diagnostics

Network problems can be caused by multiple sources . Some of
these sources are:
• Loose connections
• Incorrect wiring (including swapped wires)
• Bad grounding
• Duplicate station numbers
• Incorrect setup of drives or other devices on the network
The major diagnostic features for fault tracing on an EFB
network include Group 53 EFB Protocol parameters
5306...5309 . The Complete parameter descriptions section
describes these parameters in detail .
Diagnostic Situations
The sub-sections below describe various diagnostic situations
– the problem symptoms and corrective actions .
OM 1191 • MD5 VFD
Diagnostics on
75 .
Modbus
Last Fault
40401
40402
40403
Protocol Reference
N2
17
18
19
Normal Operation
During normal network operation, 5306...5309 parameter
values act as follows at each drive:
• 5306 EFB OK MESSAGES advances (advances for each
application message properly received and addressed to
this drive) .
• 5307 EFB CRC ERRORS does not advance at all
(advances when an invalid message CRC is received) .
• 5308 EFB UART ERRORS does not advance at all
(advances when character format errors are detected,
such as parity or framing errors) .
• 5309 EFB status value varies depending on network
traffic.
• BACnet protocol: 5316 EFB PAR 16 (MS/TP token
counter) advances for each token passed to this drive .
(Does not apply for other protocols .)
Loss of Communication
The action taken by the MD5, if communication is lost, is
configured in Communication fault. The parameters are
3018 COMM FAULT FUNC and 3019 COMM FAULT TIME .
The Complete parameter descriptions section on page 1-80
describes these parameters .
No Master Station On Line
If no master station is on line: Neither the EFB OK MESSAGES
nor the errors (5307 EFB CRC ERRORS and 5308 EFB UART
ERRORS) increase on any of the stations .
To correct:
• Check that a network master is connected and properly
programmed on the network .
• Verify that the cable is connected, and is not cut or short
circuited .
56
e
f
Mbedded
ieldbUs
FLN
BACnet
90
AV18
91
AV19
92
AV20
www .DaikinApplied .com