Group 04: Fault History - Daikin MD5 Operation Manual

Variable frequency drive controller
Table of Contents

Advertisement

Group 04: Fault History

This group stores a recent history of the faults reported by the drive .
Table 7: Group 04: Fault History
Code
Description
0401
LAST FAULT
0 – Clear the fault history (on panel = NO RECORD) .
n – Fault code of the last recorded fault . The fault code is displayed as a name . See section Fault listing on page 1-282 for the fault codes and names . The
fault name shown for this parameter may be shorter than the corresponding name in the fault listing, which shows the names as they are shown in the fault
display .
0402
FAULT TIME 1
The day on which the last fault occurred . Either as:
• A date – if real time clock is operating .
• The number of days after power on – if real time clock is not used, or was not set .
0403
FAULT TIME 2
The time at which the last fault occurred . Either as:
• Real time, in format hh:mm:ss – if real time clock is operating .
• The time since power on (minus the whole days reported in 0402), in format hh:mm:ss – if real time clock is not used, or was not set .
• Format on the Basic Control Panel: The time since power on in 2-second ticks (minus the whole days reported in 0402) . 30 ticks = 60 seconds . E .g . Value
514 equals 17 minutes and 8 seconds (= 514/30) .
0404
SPEED AT FLT
The motor speed (rpm) at the time the last fault occurred .
0405
FREQ AT FLT
The frequency (Hz) at the time the last fault occurred .
0406
VOLTAGE AT FLT
The DC bus voltage (V) at the time the last fault occurred .
0407
CURRENT AT FLT
The motor current (A) at the time the last fault occurred .
0408
TORQUE AT FLT
The motor torque (%) at the time the last fault occurred .
0409
STATUS AT FLT
The drive status (hex code word) at the time the last fault occurred .
0410
DI 1-3 AT FLT
The status of digital inputs 1...3 at the time the last fault occurred .
0411
DI 4-6 AT FLT
The status of digital inputs 4...6 at the time the last fault occurred .
0412
PREVIOUS FAULT 1
Fault code of the second last fault . Read-only .
0413
PREVIOUS FAULT 2
Fault code of the third last fault . Read-on
www .DaikinApplied .com
19
P
araMeTers
Range
Resolution
Default
Fault codes
(panel
1
0
displays as
text)
Date
dd .mm .yy
1 day
0
/ power-on
time in days
Time
2 s
0
hh:mm:ss
-32768...
1 rpm
0
+32767
-3276 .8...
0 .1 Hz
0
+3276 .7
0 .0...6553 .5
0 .1 V
0
0 .0...6553 .5
0 .1 A
0
-3276 .8...
0 .1%
0
+3276 .7
0000...
1
0
FFFF hex
000...111
(0...7
1
0
decimal)
000...111
(0...7
1
0
decimal)
As par . 0401
1
0
As par . 0401
1
0
OM 1191 • MD5 VFD