Table 11 continued: Group 16: System Controls
1608
START ENABLE 1
Selects the source of the start enable 1 signal .
Note: Start enable functionality differs from the run enable functionality .
0 = NOT SEL – Allows the drive to start without an external start enable signal .
1 = DI1 – Defines digital input DI1 as the start enable 1 signal.
• This digital input must be activated for start enable 1 signal .
• If the voltage drops and de-activates this digital input, the drive will coast to stop and show alarm 2021 on the panel display . The drive will not start until
start enable 1 signal resumes .
2...6 = DI2...DI6 – Defines digital input DI2...DI6 as the start enable 1 signal.
• See DI1 above .
7 = COMM – Assigns the fieldbus Command Word as the source for the start enable 1 signal.
• Bit 2 of the Command Word 2 (parameter 0302) activates the start disable 1 signal .
• See fieldbus user's manual for detailed instructions.
-1 = DI1(INV) – Defines an inverted digital input DI1 as the start enable 1 signal.
-2...-6 = DI2 (INV)...DI6(INV) – Defines an inverted digital input DI2...DI6 as the start enable 1 signal.
• See DI1 (INV) above .
1611
PARAMETER VIEW
Selects the parameter view, i .e . which parameters are shown .
Note: This parameter is visible only when it is activated by the optional FlashDrop device . FlashDrop is designed for fast copying of parameters to unpowered
drives . It allows easy customization of the parameter list, e .g . selected parameters can be hidden . For more information, see MFDT-01 FlashDrop User's
Manual (3AFE68591074 [English]) . FlashDrop parameter values are activated by setting parameter 9902 to 31 (LOAD FD SET) .
0 = DEFAULT – Complete long and short parameter lists are shown .
1 = FLASHDROP – FlashDrop parameter list is shown . Does not include short parameter list . Parameters that are hidden by the FlashDrop device are not
visible .
www .DaikinApplied .com
27
P
araMeTers
-6...7
1
4 (DI4)
0
0, 1
1
(DEFAULT)