• When a fault is active, the corresponding bit for the active fault is set in the Fault Words .
• Each fault has a dedicated bit allocated within Fault Words .
• See section Fault listing on page 1-282 for a description of the faults .
• The control panel displays the word in hex . For example, all zeros and a 1 in Bit 0 displays as 0001 . All zeros and a 1 in Bit 15 displays as 8000 .
Bit #
0305, FAULT WORD 1
0
OVERCURRENT
1
DC OVERVOLT
2
DEV OVERTEMP
3
SHORT CIRC
4
Reserved
5
DC UNDERVOLT
6
AI1 LOSS
7
AI2 LOSS
8
MOT OVERTEMP
9
PANEL LOSS
10
ID RUN FAIL
11
MOTOR STALL
12
CB OVERTEMP
13
EXT FAULT 1
14
EXT FAULT 2
15
EARTH FAULT
0306
FAULT WORD 2
Read-only copy of the Fault Word 2 .
• See parameter 0305 .
0307
FAULT WORD 3
Read-only copy of the Fault Word 3 .
• See parameter 0305 .
0308
ALARM WORD 1
• When an alarm is active, the corresponding bit for the active alarm is set in the Alarm Words .
• Each alarm has a dedicated bit allocated within Alarm Words .
• Bits remain set until the whole alarm word is reset . (Reset by writing zero to the word .)
• The control panel displays the word in hex . For example, all zeros and a 1 in Bit 0 displays as 0001 . All zeros and a 1 in Bit 15 displays as 8000 .