Group 64: Load Analyzer

This group defines the load analyzer, which can be used for analyzing the customer's process and sizing the drive and the motor.
The peak value is logged at 2 ms level, and the distribution loggers are updated on 0 .2 s (200 ms) time level . Three different values
can be logged .
1 . Amplitude logger 1: The measured current is logged continuously . The distribution as a percentage of the nominal current I2
is shown in ten classes .
2 . Peak value logger: One signal in group 1 can be logged for the peak (maximum) value . The peak value of the signal, peak
time (time when the peak value was detected) as well the frequency, current and DC voltage at the peak time are shown .
3 . Amplitude logger 2: One signal in group 1 can be logged for amplitude distribution . The base value (100% value) can be set
by the user .
The first logger cannot be reset. The other two loggers can be reset by a user defined method. They are also reset if either of the
signals or the peak value filter time is changed.
Table 21: Group 64: Load Analyzer
Code
Description
6401
PVL SIGNAL
Defines (by number) the signal logged for the peak value.
• Any parameter number in
100 = NOT SELECTED – No signal (parameter) logged for the peak value .
101...178 – Logs parameter 0101...0178 .
6402
PVL FILTER TIME
Defines the filter time for peak value logging.
• 0 .0...120 .0 – Filter time (seconds) .
6403
LOGGERS RESET
Defines the source for the reset of peak value logger and amplitude logger 2.
0 = NOT SEL – No reset selected .
1 = DI1 – Reset loggers on the rising edge of digital input DI1 .
2...6 = DI2...DI6 – Reset loggers on the rising edge of digital input DI2...DI6 .
7 = RESET – Reset loggers . Parameter is set to NOT SEL .
-1 = DI1(INV) – Reset loggers on the falling edge of digital input DI1 .
-2...-6 = DI2(INV) ...DI6(INV) – Reset loggers on the falling edge of digital input DI2...DI6 .
6404
AL2 SIGNAL
Defines the signal logged for amplitude logger 2.
• Any parameter number in
100 = NOT SELECTED – No signal (parameter) logged for amplitude distribution (amplitude logger 2) .
101...178 – Logs parameter 0101...0178 .
6405
AL2 SIGNAL BASE
Defines the base value from which the percentage distribution is calculated.
• Representation and default value depends on the signal selected with parameter 6404 AL2 SIGNAL .
6406
PEAK VALUE
Detected peak value of the signal selected with parameter 6401 PVL SIGNAL .
6407
PEAK TIME 1
Date of the peak value detection .
• Format: Date if the real time clock is operating (dd .mm .yy) . / The number of days elapsed after the power-on if the real time clock is not used,
or was not set (xx d) .
6408
PEAK TIME 2
Time of the peak value detection .
• Format: hours:minutes:seconds .
6409
CURRENT AT PEAK
Current at the moment of the peak value (amperes) .
6410
UDC AT PEAK
DC voltage at the moment of the peak value (volts) .
www .DaikinApplied .com
Group 01: Operating Data on page 13
Group 01: Operating Data
can be selected . Eg 102 = parameter 0102 SPEED .
can be selected . Eg 102 = parameter 0102 SPEED .
39
P
Range
Resolution
100...178
1
(OUTPUT
0 .0...120 .0 s
0 .1 s
-6...7
1
(NOT SEL)
101...178
1
(OUTPUT
Depends on
selection
Date dd .mm .yy
/ power-on time
1 d
in days
Time hh .mm .ss
2 s
0 .0...6553 .5 A
0 .1 A
0...65535 V
1 V
OM 1191 • MD5 VFD
araMeTers
n
Default
S
103
FREQ)
0 .1 s
0
103
FREQ)
60 .0 Hz