Figure 2: Parameters Mode
To change the parameters, follow these steps:
1
Select MENU to enter the main menu .
Select the Parameters mode with the UP/ DOWN buttons,
2
and select ENTER to select the Parameters Mode .
Select the appropriate parameter group with the UP/
3
DOWN buttons and select SEL .
Select the appropriate parameter in a group with the UP/
4
DOWN buttons . Select EDIT to change the parameter .
Press the UP/DOWN buttons to change the parameter
5
value .
Select SAVE to store the modified value or select
CANCEL to leave the set mode .
6
• Any modifications not saved are cancelled.
• Each individual parameter setting is valid immediately
after pressing SAVE .
Select EXIT to return to the listing of parameter groups,
7
and again to return to the main menu .
For detailed hardware description, see the
NOTE: The current parameter value appears below the
highlighted parameter .
To view the default parameter value, press the UP/
DOWN buttons simultaneously .
The most typical and necessary parameters to
change are parameter groups 99 Start-up data, 10
Start/Stop/Dir, 11 Reference Select, 20 Limits, 21
Start/Stop, 22 Accel/Decel, 26 Motor Control and 30
Fault Functions .
To restore the default factory settings, select the
application macro HVAC Default .