Group 30: Fault Functions

This group defines situations that the drive should recognize as potential faults and defines how the drive should respond if the
fault is detected .
Table 16: Group 30: Fault Functions
Code
Description
3003
EXTERNAL FAULT 1
Defines the External Fault 1 signal input and the drive response to an external fault.
0 = NOT SEL – External fault signal is not used .
1 = DI1 – Defines digital input DI1 as the external fault input.
• Activating the digital input indicates a fault . The drive displays a fault (14, EXT FAULT 1) and the drive coasts to stop .
2...6 = DI2...DI6 – Defines digital input DI2...DI6 as the external fault input.
• See DI1 above .
-1 = DI1(INV) – Defines an inverted digital input DI1 as the external fault input.
• De-activating the digital input indicates a fault . The drive displays a fault (14, EXT FAULT 1) and the drive coasts to stop .
-2...-6 = DI2(INV)...DI6(INV) – Defines an inverted digital input DI2...DI6 as the external fault input.
• See DI1(INV) above .
OM 1191 • MD5 VFD
32
P
araMeTers
Range
Resolution
Default
0 (NOT
-6...6
1
SEL)
www .DaikinApplied .com