Control Panel - Daikin MD5 Operation Manual

Variable frequency drive controller
Table of Contents

Advertisement

Status Information
Table 1: Status Information
Control Panel Display
Rotating arrow
(clockwise or counterclockwise)
Rotating dotted arrow blinking
Stationary dotted arrow
Top . The top line of the LCD display shows the basic status
information of the drive .
• HAND – Indicates that the drive control is local, that is,
from the control panel .
• AUTO – Indicates that the drive control is remote, such
as the basic I/O (X1) or fieldbus.
– Indicates the drive and motor rotation status as
follows:
Upper right – shows the active reference .
Middle . Using
Group 34: Panel
display can be configured to display:
• One to three parameter values
– The default display shows
parameters 0103 (OUTPUT
FREQ) in percentages, 0104
(CURRENT) in amperes and
0120 (AI1) in milliamperes .
— Use parameters 3401, 3408, and 3415, see
34, to select the parameters (from Group 01) to
display . Entering "parameter" 0100 results in no
parameter displayed . For example, if 3401 = 0100
and 3415 = 0100, then only the parameter specified
by 3408 appears in the Control Panel display .
— You can also scale each parameter in the display, for
example, to convert the motor speed to a display of
conveyor speed . Parameters 3402...3405 scale the
parameter specified by 3401, parameters 3409...3412
scale the parameter specified by 3408, etc.
• A bar meter rather than one of the parameter values .
— Enable bar graph displays
using parameters 3404,
3411 and 3418 .
Bottom . The bottom of the LCD
display shows:
• Lower corners – show the functions currently assigned
to the two soft keys .
• Lower middle – displays the current time (if configured to
show the time) .
OM 1191 • MD5 VFD
Significance
• Drive is running and at setpoint
• Shaft direction is forward or reverse
Drive is running but not at setpoint
Start command is present, but motor
is not running . E .g . start enable is
missing .
Display, the middle of the LCD
page
Operating the Drive
Auto/Hand – The very first time the drive is powered up, it is
in the auto control (AUTO) mode, and is controlled from the
Control terminal block X1 .
To switch to hand control (HAND) and control the drive using
the control panel, press and hold the
• Pressing the HAND button switches the drive to hand
control while keeping the drive running .
• Pressing the OFF button switches to hand control and
stops the drive .
To switch back to auto control (AUTO), press and hold the
button .
Hand/Auto/Off – To start the drive press the HAND or AUTO
buttons, to stop the drive press the OFF button .
Reference – To modify the reference (only possible if the
display in the upper right corner is in reverse video) press the
UP or DOWN buttons (the reference changes immediately) .
The reference can be modified in the local control mode
(HAND/OFF), and can be parameterized (using
Reference
Select) to also allow modification in the remote
control mode .
NOTE: The Start/Stop, Shaft direction and Reference
functions are only valid in local control (HAND/OFF)
mode .
6
C
P
onTrol
anel
C
P
onTrol
anel
or
button .