Communication Setup - Efb; Serial Communication Selection; Serial Communication Configuration - Daikin MD5 Operation Manual

Variable frequency drive controller
Table of Contents

Advertisement

Communication Setup – EFB

Serial Communication Selection

To activate the serial communication, set parameter 9802
COMM PROTOCOL SEL =
• 1 (STD MODBUS) .
• 2 (N2)
• 3 (FLN)
• 5 (BACNET)
NOTE: If you cannot see the desired selection on the panel,
your drive does not have that protocol software in the
application memory .
Table 25: Serial Communication Configuration
Code
Description
EFB PROTOCOL ID
5301
Contains the identification and
program revision of the protocol .
EFB STATION ID
5302
Defines the node address of the
RS485 link .
EFB BAUD RATE
Defines the communication speed
of the RS485 link in kbits per
second (kbits/s) .
1 .2 kbits/s
2 .4 kbits/s
5303
4 .8 kbits/s
9 .6 kbits/s
19 .2 kbits/s
38 .4 kbits/s
57 .6 kbits/s
76 .8 kbits/s
EFB PARITY
Defines the data length, parity
and stop bits to be used with the
RS485 link communication .
• The same settings must be used
in all on-line stations .
0 = 8N1 – 8 data bits, No parity,
5304
one stop bit .
1 = 8N2 – 8 data bits, No parity,
two stop bits .
2 = 8E1 – 8 data bits, Even parity,
one stop bit .
3 = 8O1 – 8 data bits, Odd parity,
one stop bit .
NOTE: For the BACnet protocol, the MD5 will function as
a Master with MAC IDs in the range of 1 - 127 . With
MAC ID settings of 128 - 254, the drive is in Slave
only behavior .
OM 1191 • MD5 VFD
Modbus
Do not edit . Any non-zero value entered for parameter 9802 COMM PROT SEL, sets this parameter automatically . The
format is: XXYY, where xx = protocol ID, and YY = program revision .
When one of these protocols is selected, the default value for this parameter is: 1
Set each drive on the network with a unique value for this parameter .
Note: For a new address to take affect, the drive power must be cycled OR 5302 must first be set to 0 before selecting
a new address . Leaving 5302 = 0 places the RS485 channel in reset, disabling communication .
When this protocol is selected, the default value for this parameter is
9 .6
9 .6 Do not edit .
When this protocol is
selected, the default value
When this protocol is selected, the default value for this parameter is: 0 Do not edit .
for this parameter is: 1

Serial Communication Configuration

Setting 9802 automatically sets the appropriate default values
in parameters that define the communication process. These
parameters and descriptions are defined below. In particular,
note that the station ID may require adjustment .
EFB Protocol Reference
N2
4 .8 Do not edit .
48
e
f
Mbedded
FLN
BACnet
When this protocol is
selected, the default value
for this parameter is: 128
When this protocol is
selected, the default value
for this parameter is: 38400 .
www .DaikinApplied .com
ieldbUs