Analog Output Object Instance Summary; Analog Value Object Instance Summary - Daikin MD5 Operation Manual

Variable frequency drive controller
Table of Contents

Advertisement

Analog Output Object Instance Summary

The following table summarizes the Analog Output Objects supported:
Table 41: Analog Output Objects
Instance ID
Object Name
AO0
AO 1 COMMAND
AO1
AO 2 COMMAND
NOTE: For Present Value Access Types, R = Read-only,
W = Writeable, C = Commandable . Commandable
values support priority arrays & relinquish defaults .

Analog Value Object Instance Summary

The following table summarizes the Analog Value Objects supported:
Table 42: Analog Value Objects
Instance
Object Name
ID
AV0
OUTPUT SPEED This object indicates the calculated motor speed in RPM . The corresponding drive parameter is 0102 .
This object indicates the output frequency applied to the motor in Hz . The corresponding drive
AV1
OUTPUT FREQ
parameter is 0103 .
AV2
DC BUS VOLT
This object indicates the drive's DC bus voltage level . The corresponding drive parameter is 0107 .
This object indicates the AC output voltage applied to the motor . The corresponding drive parameter is
AV3
OUTPUT VOLT
0109 .
AV4
CURRENT
This object indicates the measured output current . The corresponding drive parameter is 0104 .
This object indicates the calculated motor output torque as a percentage of nominal torque . The
AV5
TORQUE
corresponding drive parameter is 0105 .
AV6
POWER
This object indicates the measured output power in kW . The corresponding drive parameter is 0106 .
This object indicates the measured heatsink temperature in °C . The corresponding drive parameter is
AV7
DRIVE TEMP
0110 .
This object indicates, in kW hours, the drive's accumulated energy usage since the last reset . The
AV8
KWH (R)
value can be reset to zero . The corresponding drive parameter is 0115 .
AV9
KWH (NR)
This object indicates the drive's accumulated energy usage in kW hours . The value cannot be reset .
AV10
PRC PID FBCK
This object is the Process PID feedback signal . The corresponding drive parameter is 0130 .
This object is the Process PID output signal's deviation from its setpoint . The corresponding drive
AV11
PRC PID DEV
parameter is 0132 .
AV12
EXT PID FBCK
This object is the External PID feedback signal . The corresponding drive parameter is 0131 .
This object is the External PID output signal's deviation from its setpoint . The corresponding drive
AV13
EXT PID DEV
parameter is 0133 .
This object indicates, in hours, the drive's accumulated run time since the last reset . The value can be
AV14
RUN TIME (R)
reset to zero . The corresponding drive parameter is 0114 .
AV15
MOTOR TEMP
This object indicates the drive's motor temperature .
AV16
INPUT REF 1
This object sets Input Reference 1 . Control requires parameter 1103 value = COMM .
This object sets either:
• Input Reference 2 . Control requires parameter 1106 value = COMM .
AV17
INPUT REF 2
• Process PID setpoint . Control requires parameter 1106 value = PID1 OUT and parameter 4010 value
= COMM .
This object indicates the most recent fault entered in the drive's fault log . The corresponding drive
AV18
LAST FLT
parameter is 0401 .
This object indicates the second most recent fault entered in the drive's fault log . The corresponding
AV19
PREV FLT 1
drive parameter is 0412 .
This object indicates the third most recent fault entered in the drive's fault log . The corresponding drive
AV20
PREV FLT 2
parameter is 0413 .
AV21
AO 1 ACT
This object indicates Analog Output 1's level . The corresponding drive parameter is 0124 .
AV22
AO 2 ACT
This object indicates Analog Output 2's level . The corresponding drive parameter is 0125 .
AV23
ACCEL1 TIME
This object sets the Ramp1 acceleration time . The corresponding drive parameter is 2202 .
AV24
DECEL1 TIME
This object sets the Ramp1 deceleration time . The corresponding drive parameter is 2203 .
This object defines the parameter to be read or written to by the mailbox function. See BV15 and
AV25
MBOX PARAM
BV16 .
Table 42 continued: Analog Value Objects
www .DaikinApplied .com
This object controls Analog Output 1 . The corresponding drive parameter is 0135, COMM
VALUE 1 . Control requires parameter 1501 value = 135 .
This object controls Analog Output 2 . The corresponding drive parameter is 0136, COMM
VALUE 2 . Control requires parameter 1507 value = 136 .
Description
Description
61
e
f
Mbedded
ieldbUs
Present Value
Units
Access Type
Percent
C
Percent
C
Present Value
Units
Access Type
RPM
R
Hertz
R
Volts
R
Volts
R
Amps
R
Percent
R
Kilowatts
R
°C
R
kWh
W
kWh
R
Percent
R
Percent
R
Percent
R
Percent
R
Hours
W
°C
R
Percent
C
Percent
C
None
R
None
R
None
R
Milliamps
R
Milliamps
R
Seconds
W
Seconds
W
None
W
OM 1191 • MD5 VFD