Table 54 continued: Alarms by Code Numbers
Fault Code
Fault Name In Panel
2010
MOT OVERTEMP
2011
UNDERLOAD
2012
MOTOR STALL
2013 (note 1)
AUTORESET
2014 (note 1)
AUTOCHANGE
2015
PFA INTERLOCK
2016
Reserved
2017
OFF BUTTON
2018 (note 1)
PID SLEEP
2019
ID RUN
2020
OVERRIDE
START ENABLE 1
2021
MISSING
START ENABLE 2
2022
MISSING
2023
EMERGENCY STOP
2024
ENCODER ERROR
2025
FIRST START
2026
RESERVED
2027
USER LOAD CURVE
2028
START DELAY
NOTE: Even when the relay output is configured to indicate
alarm conditions (e .g . parameter 1401 RELAY
OUTPUT 1 = 5 (ALARM) or 16 (FLT/ALARM)), this
alarm is not indicated by a relay output .
www .DaikinApplied .com
Description and Recommended Corrective Action
Motor is hot, based on either the drive's estimate or on temperature feedback . This alarm warns that a Motor Underload
fault trip may be near . Check:
• Check for overloaded motor .
• Adjust the parameters used for the estimate (3005...3009) .
• Check the temperature sensors .
Motor load is lower than expected . This alarm warns that a Motor Underload fault trip may be near . Check:
• Motor and drive ratings match (motor is NOT undersized for the drive)
Motor is operating in the stall region . This alarm warns that a Motor Stall fault trip may be near .
This alarm warns that the drive is about to perform an automatic fault reset, which may start the motor .
• To control automatic reset, use parameter
This alarm warns that the PFA autochange function is active .
• To control PFA, use parameter
This alarm warns that the PFA interlocks are active, which means that the drive cannot start the following:
• Any motor (when Autochange is used),
• The speed regulated motor (when Autochange is not used) .
Note 1 .
This alarm warns that the PID sleep function is active, which means that the motor could accelerate when the PID sleep
function ends .
• To control PID sleep, use parameters 4022*...4026* or 4122*...4126 .*
*Not used with MicroTech II .
Performing ID run .
This alarm warns that the Override function is active, which may start the motor .
This alarm warns that the Start Enable 1 signal is missing .
• To control Start Enable 1 function, use parameter 1608 .
To correct, check:
• Digital input configuration.
• Communication settings .
This alarm warns that the Start Enable 2 signal is missing .
• To control Start Enable 2 function, use parameter 1609 .
To correct, check:
• Digital input configuration.
• Communication settings .
Emergency stop activated .
The drive is not detecting a valid encoder signal . Check for and correct:
• Encoder presence and proper connection (reverse wired, loose connection, or short circuit) .
• Voltage logic levels are outside of the specified range.
• A working and properly connected Pulse Encoder Interface Module, OTAC-01 .
Signals that a the drive is performing a First Start evaluation of motor characteristics. This is normal the first time the
motor is run after motor parameters are entered or changed . See parameter 9910 (MOTOR ID RUN) for a description of
motor models .
Not used .
This alarm warns that the condition defined by parameter 3701 USER LOAD C MODE has been valid longer that half of
the time defined by 3703 USER LOAD C TIME.
Contact your local Daikin sales representative if there is a problem .
Shown during the Start delay . See parameter 2113 START DELAY .
Contact your local Daikin sales representative if there is a problem .
79
Group 31: Automatic Reset on page
Group 81: PFA Control on page 41
d
iagnosTiCs
33 .