Pid Control Setpoint Source; Communication Fault; Feedback From The Drive - Fba - Daikin MD5 Operation Manual

Variable frequency drive controller
Table of Contents

Advertisement

PID Control Setpoint Source

Using the fieldbus for the PID control setpoint requires:
Table 50: Setpoint Values
Drive Parameter
4010
SETPOINT SEL

Communication Fault

When using fieldbus control, specify the drive's action if serial
communication is lost .
Table 51: Communication Fault
Drive Parameter
3018
COMM FAULT FUNC
3019
COMM FAULT TIME
Feedback from the Drive – FBA
Inputs to the controller (drive outputs) have pre-defined
meanings established by the protocol . This feedback does not
require drive configuration. The following table lists a sample of
feedback data . For a complete listing, see all parameters listed
in Complete parameter descriptions .
Table 52: Sample of Feedback Data
Drive Parameter
0102
0103
0104
0105
0106
0107
0109
0301
0301
0118
www .DaikinApplied .com
Value
8 (COMM VALUE 1)
9 (COMM + AI1)
10 (COMM*AI1)
Value
0 (NOT SEL)
1 (FAULT)
2 (CONST SP7)
3 (LAST SPEED)
Set time delay before
acting on a communication
loss .
SPEED
FREQ OUTPUT
CURRENT
TORQUE
POWER
DC BUS VOLT
OUTPUT VOLTAGE
FB STATUS WORD – bit 0 (STOP)
FB STATUS WORD – bit 2 (REV)
DI1-3 STATUS – bit 1 (DI3)
71
• Drive parameter values set as defined below.
• Fieldbus controller supplied setpoint value in the
appropriate location. (As defined in Analog output control
above .)
Description
Setpoint is 0135 value (+/-/* AI1)
Description
Set for appropriate drive response .
Scaling
To scale the drive parameter values see the Actual value
scaling in the following sections, as appropriate:
• Daikin drives profile technical data
• Generic profile technical data
f
a
ieldbUs
daPTer
Protocol Reference
Protocol Reference
Protocol Reference
OM 1191 • MD5 VFD