Table 25 continued: Serial Communication Configuration
Code
Description
EFB CTRL PROFILE
Selects the communication profile
used by the EFB protocol .
0 = Daikin DRV LIM – Operation
of Control/Status Words
conform to Daikin Drives
Profile (limited), as used in
5305
ACH400/550 .
1 = DCU PROFILE – Operation of
Control/Status Words conform
to 32-bit DCU Profile.
2 = Daikin DRV FULL – Operation
of Control/Status Words
conform to Daikin Drives
Profile (full).
5306
EFB OK MESSAGES
5307
EFB CRC ERRORS
5308
EFB UART ERRORS
5309
EFB STATUS
5310
EFB PAR10
5311
EFB PAR11
5314
EFB PAR14
5315
EFB PAR15
5316
EFB PAR 16
5317
EFB PAR17
NOTE: After any changes to the communication settings,
protocol must be reactivated by either cycling the
drive power, or by setting parameter 5302 EFB
STATION ID to 0 and then restoring the station ID
(5302) or use Reinitialize Device Service
www .DaikinApplied .com
Modbus
When this protocol is
N/A . When this protocol is selected, the default value for this parameter is: 0 . Changing
selected, the default value
the value for this parameter has no affect on this protocol's behavior .
for this parameter is: 0
This parameter indicates the number of valid application messages received at this drive . This count does not include
MS/TP token passing and polling messages . (For such messages, see 5316) .
This parameter indicates the number of CRC errors detected, in either the header or data CRCs .
This parameter indicates the number of UART-related errors (framing, parity) detected .
This parameter indicates the internal status of the EFB Protocol as follows:
• IDLE – EFB Protocol is configured but not receiving messages.
• TIMEOUT – Time between valid messages has exceeded the interval set by parameter 3019 .
• OFFLINE – EFB Protocol is receiving messages NOT addressed to this drive .
• ONLINE – EFB Protocol is receiving messages addressed to this drive .
• RESET – EFB Protocol is in reset .
• LISTEN ONLY – EFB Protocol is in listen-only mode .
Sets the response turnaround time in milliseconds in addition to any fixed delay imposed
Not used for Comm setup .
by the protocol . When this protocol is selected, the default value is:
3 ms
Not used for Comm setup .
Not used for Comm setup .
Not used for Comm setup .
Not used for Comm setup .
49
EFB Protocol Reference
N2
FLN
0 ms
e
f
Mbedded
ieldbUs
BACnet
5 ms
This parameter, together
with parameter 5317, EFB
PAR 17, sets BACnet
Device Object Instance IDs:
• For the range 1 to 65,535:
Thips parameter sets the
ID directly (5317 must
be 0) . For example, the
following values set the ID
to 49134: 5311 = 49134
and 5317 = 0 .
• For IDs > 65,335: The
ID equals 5311's value
plus 10,000 times 5317's
value . For examle, the
following values set the
ID to 71234: 5311 = 1234
and 5317 = 7 .
This parameter indicates
the count of MS/TP tokens
passed to this drive .
This parameter works
with parameter 5311 to
set BACnet Device Object
Instance IDs . See parameter
5311,
page
38 .
OM 1191 • MD5 VFD