Wall or cabinet mountable drive for controlling ac motors (116 pages)
Summary of Contents for Daikin Maverick I
Page 1
Operation Manual OM 1077-1 Group: Applied Air Systems Part Number: OM 1077 Date: July 2016 Maverick I Package Air Conditioner ® DDC Rooftop Unit Controller Heating & Cooling, Gas/Electric and Electric/Electric Models MPS 003B – 025B 3 to 25 Tonns [10.6 to 87.9 kW] R-410A Refrigerant...
General Read this manual and any instructions packaged with separate The Maverick I 3 to 25 ton Package has a Rooftop Unit equipment prior to installation. Give this manual to the owner Controller factory mounted and wired in their respective control and explain its provisions.
The DDC Controller in each Maverick I 3 to 25 ton Package Air • Staging. Depending on the unit controls up to 2 stages...
Page 5
MOD1 LED blinks when the control is communicating on the internal network between the IFC and/or economizer MOD2 LED MOD2 LED blinks when the control is communicating between the DDC Controller and field installed communication card www.DaikinApplied.com OM 1077-1 • MAVERICK I...
If the remote set point adjustment is enabled but the input reads an invalid number, the control will default back to the occupied set point selection. OM 1077-1 • MAVERICK I www.DaikinApplied.com...
Page 7
LCD display if the pressure differential indicates that the indoor blower is not operating. The control will also monitor the system and if the blower is running and is not required a fault will be sent to the DDC Controller. www.DaikinApplied.com OM 1077-1 • MAVERICK I...
24 V thermostat equipped with an “L” 18 AWG Wall mounted sensor terminal. 113117701 Solid 3/C CL2P with tenant override Thermostat Wall mounted sensor 18 AWG with space point 113117701 Solid 3/C CL2P adjustment Thermostat OM 1077-1 • MAVERICK I www.DaikinApplied.com...
Figure 2. This is necessary to meet National Electrical Code (NEC) and UL 1995 requirements for separation of high and low Conduit for Low voltage circuits. Voltage Conductors www.DaikinApplied.com OM 1077-1 • MAVERICK I...
Occupancy Compressor Signal Indoor Fan 2nd Stage Heat 24V Common 1st Stage Heat Figure 4: Standalone with Zone Sensor and Time Clock Zone Sensor 10k Thermistor Time Clock Override Button 10k Pot Setpoint Adj. OM 1077-1 • MAVERICK I www.DaikinApplied.com...
2nd-party building automation system that will be controlled from a central location. Figure 5: Zone Sensor with Building Automation System Zone Sensor 10k Thermistor Override Button 10k Pot Setpoint Adj. BACnet Daughter Board LONWorks Daughter Board www.DaikinApplied.com OM 1077-1 • MAVERICK I...
BAS communication card and a third-party BAS that will be controlled from a central location. Figure 6: Indoor Relative Humidity Connection 24VDC Humidity Sensor OM 1077-1 • MAVERICK I www.DaikinApplied.com...
IFC will respond with a fault code and it will flash code “2” on the LED, waiting indefinitely for both pressure switches to open. If both pressure switches are open, the IFC proceeds to prepurge. www.DaikinApplied.com OM 1077-1 • MAVERICK I...
Page 14
Low gas, low inducer, and the delay OFF time. blower remain energized. If the DDC Controller calls for 2nd stage heat (Hi Heat), the IFC transitions to high heat. OM 1077-1 • MAVERICK I www.DaikinApplied.com...
Page 15
The continuous fan operation continues to function while the purge time with high gas output energized to begin a re-ignition control is in heat mode lockout. attempt. The indoor blower remains on (for the delay OFF time) through the re-ignition attempt. www.DaikinApplied.com OM 1077-1 • MAVERICK I...
Page 16
The electric heat is energized whenever the demand for heat unburned gas. is not satisfied. The heat source it will be staged on based on demand. During electric heat operation the control does not delay energizing the indoor fan. OM 1077-1 • MAVERICK I www.DaikinApplied.com...
Enter key again for the change to take effect. During the adjustment, either left or right keys work as “escape” so the parameter reverts back to its original value and the cursor is no longer visible. Left Right Enter Down www.DaikinApplied.com OM 1077-1 • MAVERICK I...
Page 18
Defrost Mode Eff. DCV Level All Sub-Menus highlighted gray Acc defrost time Dff. Eco Position are user adjustable Defrost SCT lim. Eff. Min. Position Defrost Comp. Off Local Min. Pos. Econ. Faults Econ Firm Vrsn OM 1077-1 • MAVERICK I www.DaikinApplied.com...
2 seconds. The Tenant Override period is adjustable between 2 and 6 hours and it has priority over any other settings. All set points are available via network and local human interface. OM 1077-1 • MAVERICK I www.DaikinApplied.com...
The DDC Controller will consider the hardwired potentiometer reading or the network remote set point adjustment as the cooling set point. It calculates the heating set point by subtracting dead band (2.0°F) and differential from the cooling set point. www.DaikinApplied.com OM 1077-1 • MAVERICK I...
Eff.Eco.Position 5°F below the set point. Eff.Min.Position Local. Min. Pos. DCV Sensor Fault OAE Sensor Fault Econ. Faults RAE Sensor Fault MAT Sensor Fault Econ Firm Vrsn 0103 * Menus that are user adjustable OM 1077-1 • MAVERICK I www.DaikinApplied.com...
Page 23
The economizer will allow the dampers to close more than the minimum position if the indoor air quality is not contaminated. The Econ. DCV Limit can be set from 0 to 100% but must be lower than the minimum position. www.DaikinApplied.com OM 1077-1 • MAVERICK I...
Note: The actuator fault must be present for at least 2 minutes with the unit powered, the indoor fan running, and the outside damper commanded to open more than 0% before the alarm is set. OM 1077-1 • MAVERICK I www.DaikinApplied.com...
The anti short cycle delay is an adjustable delay used to keep button on the space sensor for more than 2 seconds. the compressor from re-energizing too quickly after a cycle. The delay time starts after the compressor de-energizes. www.DaikinApplied.com OM 1077-1 • MAVERICK I...
Table 14 Table 15 explain the various modes available. OM 1077-1 • MAVERICK I www.DaikinApplied.com...
Page 27
Y1 - First stage cooling call from thermostat or network Y2 - Second stage cooling call from thermostat or network *1st stage cooling speed has a default value of 50% of high fan speed www.DaikinApplied.com OM 1077-1 • MAVERICK I...
NOTE: If the indoor fan is ramping up to speed from a dead stop, the Low Fan Speed will briefly ramp to 75% of the full speed in order to “set” the fan proving switch and confirm proof of indoor airflow. OM 1077-1 • MAVERICK I www.DaikinApplied.com...
• Expansion valve in not operating AC Low Pressure Switch 2 Trip-LP2 DDC Controller outdoor ambient temperature rises above 5 °F. LPS correctly is ignored during defrost. www.DaikinApplied.com OM 1077-1 • MAVERICK I...
Page 30
• Low line voltage to compressor Duct High Limit Fault Future implementation Indicates that a combination of thermostat inputs Invalid Thermostat selection is invalid. Leave inducer de-energized until pressure switch Pressure Switch 1 Closed • Bad Pressure Switch open OM 1077-1 • MAVERICK I www.DaikinApplied.com...
Page 31
• Broken belt • Indoor motor running backwards (3 phase) • Open internal motor protector • Replace the sensor ELM - OAE Sensor Fail Sensor short, failure • Check sensor is installed correctly on control www.DaikinApplied.com OM 1077-1 • MAVERICK I...
Page 32
• Replace the sensors Indicate presence of the alarm and convert Space Sensor & Return Sensor Fail DDC Controller • Check sensors are installed correctly operation to thermostat mode. on control OM 1077-1 • MAVERICK I www.DaikinApplied.com...
Page 33
Three occurrences of a high pressure High Pressure – Circuit 2 Problem - Lockout DDC Controller switch within the same call will lock the circuit out. • Excessive refrigerant charge The lockout is reset by removing the call. www.DaikinApplied.com OM 1077-1 • MAVERICK I...
3. Wait until cursor on display flashes 4. SCROLL DOWN OCCUPIED MODE 5. Chose Ctrl by Tstat Ctrl by Tstat All Sub-Menus highlighted gray are 6. Briefly press [Enter] user adjustable UNIT 7. Wait until cursor stops flashing KEYPAD OM 1077-1 • MAVERICK I www.DaikinApplied.com...
Page 48
Daikin Applied Training and Development Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.