Group 01: Operating Data

This group contains drive operating data, including actual signals . The drive sets the values for actual signals, based on
measurements or calculations . You cannot set these values .
Table 5: Group 01: Operating Data
Code
Description
0101
SPEED & DIR
The calculated signed speed of the motor (rpm) . The absolute value of 0101 SPEED & DIR is the same as the value of 0102 SPEED .
• The value of 0101 SPEED & DIR is positive if the motor runs in the forward direction .
• The value of 0101 SPEED & DIR is negative if the motor runs in the reverse direction .
0102
SPEED
The calculated speed of the motor (rpm) .
0103
OUTPUT FREQ
The frequency (Hz) applied to the motor .
0104
CURRENT
The motor current, as measured by the MD5 .
0105
TORQUE
Output torque . Calculated value of torque on motor shaft in % of motor nominal torque .
0106
POWER
The measured motor power in kW .
0107
DC BUS VOLTAGE
The DC bus voltage in V DC, as measured by the MD5 .
0109
OUTPUT VOLTAGE
The voltage applied to the motor .
0110
DRIVE TEMP
The temperature of the drive power transistors in degrees Celsius .
0111
EXTERNAL REF
External reference, REF1, in rpm or Hz – units determined by parameter 9904 .
0112
EXTERNAL REF 2
External reference, REF2, in % .
0113
CTRL LOCATION
Active control location . Alternatives are:
0 = LOCAL
1 = EXT1
2 = EXT2
0114
RUN TIME (R)
The drive's accumulated running time in hours (h) .
• Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode .
0115
KWH COUNTER (R
The drive's accumulated power consumption in kilowatt hours .
• The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0 .
• Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode . MD5-UH User's Manual 1-83 Parameters
0116
APPL BLK OUTPUT
Application block output signal . Value is from either:
• PFA control, if PFA Control is active, or
• Parameter 0112 EXTERNAL REF 2 .
www .DaikinApplied .com
13
P
araMeTers
Range
Resolution
Default
-30000...
1 rpm
30000 rpm
0...30000
1 rpm
rpm
0 .0...500 .0
0 .1 Hz
Hz
0 .0...1 .5
0 .1 A
× I2
n
-200 .0...
0 .1%
200 .0%
-1 .5...1 .5
0 .1 kW
× P
n
0...2 .5 ×
1 V
VdN
0...2 .0 ×
1 V
V
dN
0 .0...150 .0
0 .1 °C
°C
1
0 .0...500 .0
0 .1 Hz / 1
Hz /
rpm
0...30000
rpm
0 .0...100 .0%
(0 .0...600 .0%
0 .1%
for torque)
0...2
1
0...9999 h
1 h
0...65535
1 kWh
kWh
0 .0...100 .0%
(0 .0...600 .0%
0 .1%
for torque)
OM 1191 • MD5 VFD