Group 53: Efb Protocol - Daikin MD5 Operation Manual

Variable frequency drive controller
Table of Contents

Advertisement

Group 53: EFB Protocol

This group defines set-up variables used for an embedded fieldbus (EFB) communication protocol. The standard EFB protocol in
the MD5 is Modbus . See chapter
Table 20: Group 53: EFB Protocol
Code
Description
5302
EFB STATION ID
Defines the node address of the RS485 link.
• The node address on each unit must be unique .
5303
EFB BAUD RATE
Defines the communication speed of the RS485 link in kbits per second (kb/s).
1 .2 kb/s
2 .4 kb/s
19 .2 kb/s
38 .4 kb/s
5304
EFB PARITY
Defines the data length, parity and stop bits to be used with the RS485 link communication.
• The same settings must be used in all on-line stations .
0 = 8 NONE 1 – 8 data bits, no parity, one stop bit .
1 = 8 NONE 2 – 8 data bits, no parity, two stop bits .
2 = 8 EVEN 1 – 8 data bits, even parity, one stop bit .
3 = 8 ODD 1 – 8 data bits, odd parity, one stop bit .
5306
EFB OK MESSAGES
Contains a count of valid messages received by the drive .
• During normal operation, this counter is increasing constantly .
5307
EFB CRC ERRORS
Contains a count of the messages with a CRC error received by the drive . For high counts, check:
• Ambient electro-magnetic noise levels – high noise levels generate errors .
• CRC calculations for possible errors .
5308
EFB UART ERRORS
Contains a count of the messages with a character error received by the drive .
5309
EFB STATUS
Contains the status of the EFB protocol .
0 = IDLE – EFB protocol is configured, but not receiving any messages.
1 = EXECUT INIT – EFB protocol is initializing .
2 = TIME OUT – A timeout has occurred in the communication between the network master and the EFB protocol .
3 = CONFIG ERROR – EFB protocol has a configuration error.
4 = OFF-LINE – EFB protocol is receiving messages that are NOT addressed to this drive .
5 = ON-LINE – EFB protocol is receiving messages that are addressed to this drive .
6 = RESET – EFB protocol is performing a hardware reset .
7 = LISTEN ONLY – EFB protocol is in listen-only mode .
5311
EFB PAR 11
Specifies the parameter mapped to Modbus Register 40006.
5312
EFB PAR 12
Specifies the parameter mapped to Modbus Register 40007.
5313
EFB PAR 13
Specifies the parameter mapped to Modbus Register 40008.
OM 1191 • MD5 VFD
Embedded Fieldbus on page
4 .8 kb/s
9 .6 kb/s
57 .6 kb/s
76 .8 kb/s
45 .
38
P
araMeTers
Range
Resolution
Default
1 = SAF
0...65535
2 = RAF/EAF
3 = ERW
1 .2, 2 .4, 4 .8,
9 .6, 19 .2,
9 .6 kb/s
38 .4, 57 .6,
76 .8 kb/s
0...3
1
(8 NONE 1)
0...65535
1
0...65535
1
0...65535
1
0...7
1
0 (IDLE)
0...65535
1
0...65535
1
0...65535
1
www .DaikinApplied .com
S
1
0
0
0
0
0
0
0