Diagnostics - Fba; Fault Handling; Serial Communication Diagnostics - Daikin MD5 Operation Manual

Variable frequency drive controller
Table of Contents

Advertisement

Diagnostics – FBA

Fault Handling

The MD5 provides fault information as follows:
• The control panel display shows a fault code and text .
See
page 74
for a complete description .
• Parameters 0401 LAST FAULT, 0402 PREVIOUS
FAULT1 and 0403 PREVIOUS FAULT2 store the most
recent faults .
• For fieldbus access, the drive reports faults as a
hexadecimal value, assigned and coded according to
the DRIVECOM specification. See table below. Not
all profiles support requesting fault codes using this
specification. For profiles that support this specification,
the profile documentation defines the proper fault request
process .
Table 53: Drive Fault Code
Drive Fault Code
1
OVERCURRENT
2
DC OVERVOLT
3
DEV OVERTEMP
4
SHORT CIRC
5
Reserved
6
DC UNDERVOLT
7
AI1 LOSS
8
AI2 LOSS
9
MOT TEMP
10
PANEL LOSS
11
ID RUN FAIL
12
MOTOR STALL
14
EXTERNAL FLT 1
15
EXTERNAL FLT 2
16
EARTH FAULT
17
UNDERLOAD
18
THERM FAIL
19
OPEX LINK
20
OPEX PWR
21
CURR MEAS
22
SUPPLY PHASE
23
ENCODER ERR
24
OVERSPEED
25
Reserved
26
DRIVE ID
27
CONFIG FILE
28
SERIAL 1 ERR
29
EFB CONFIG FILE
30
FORCE TRIP
31
EFB 1
32
EFB 2
OM 1191 • MD5 VFD
Fieldbus Fault Code
(DRIVECOM specification)
2310h
3210h
4210h
2340h
FF6Bh
3220h
8110h
8110h
4310h
5300h
FF84h
7121h
9000h
9001h
2330h
FF6Ah
5210h
7500h
5414h
2211h
3130h
7301h
7310h
FF80h
5400h
630Fh
7510h
6306h
FF90h
FF92h
FF93h
72

Serial Communication Diagnostics

Besides the drive fault codes, the FBA module has diagnostic
tools . Refer to the user's manual supplied with the FBA
module .
Drive Fault Code
33
EFB 3
34
MOTOR PHASE
35
OUTPUT WIRING
36
INCOMP SWTYPE
101
SERF CORRUPT
102
Reserved
103
SERF MACRO
104
Reserved
105
Reserved
201
DSP T1 OVERLOAD
202
DSP T2 OVERLOAD
203
DSP T3 OVERLOAD
204
DSP STACK ERROR
205
Reserved
206
OMIO ID ERROR
207
EFB LOAD ERR
1000
PAR HZRPM
1001
PAR PFAREFNG
1002
Reserved (obsolete)
1003
PAR AI SCALE
1004
PAR AO SCALE
1005
PAR PCU 2
1006
EXT ROMISSING
1007
PAR FBUSMISSING
1008
PAR PFAWOSCALAR
1009
PAR PCU 1
1010
PAR PFA OVERRIDE
1011
PAR OVERRIDE PARS
1012
PAR PFC IO 1
1013
PAR PFC IO 2
1014
PAR PFC IO 3
f
a
ieldbUs
daPTer
Fieldbus Fault Code
(DRIVECOM specification)
FF94h
FF56h
FF95h
630Fh
FF55h
FF55h
FF55h
FF55h
FF55h
6100h
6100h
6100h
6100h
5000h
5000h
6100h
6320h
6320h
6320h
6320h
6320h
6320h
6320h
6320h
6320h
6320h
6320h
6320h
6320h
6320h
6320h
www .DaikinApplied .com

Advertisement

Table of Contents
loading