Table 5 continued: Group 01: Operating Data
0145
MOTOR TEMP
Motor temperature in degrees Celsius / PTC resistance in ohms .
• Applies only if motor temperature sensor is set up .
0150
CB TEMP
Temperature of the drive control board in degrees Celsius .
Note: Some drives have a control board (OMIO) that does not support this feature . These drives always show the constant value of 25 .0 °C .
0153
MOT THERM STRESS
Estimated rise of the motor temperature . Value equals to the estimated motor thermal stress as a percentage of the motor temperature trip level .
0158
PID COMM VALUE 1
Data received from fieldbus for PID control (PID1 and PID2).
0159
PID COMM VALUE 2
Data received from fieldbus for PID control (PID1 and PID2).
0174
SAVED KWH
Energy saved in kWh compared to the energy used when the pump is connected directly to the supply . See the note on page 1-163 .
• The counter value is accumulated till it reaches 999 .9 after which the counter rolls over and starts again from 0 .0 .
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time) .
0175
SAVED MWH
Energy saved in MWh compared to the energy used when the pump is connected directly to the supply . See the note on page 1-163 .
• The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0 .
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time) .
0176
SAVED AMOUNT 1
Energy saved in local currency (remainder when the total saved energy is divided by 1000) . See the note on page 1-163 .
• To find out the total saved energy in currency units, add the value of parameter 0177 multiplied by 1000 to the value of parameter 0176.
Example:
0176 SAVED AMOUNT 1 = 123 .4
0177 SAVED AMOUNT 2 = 5
Total saved energy = 5 ×1000 + 123 .4 = 5123 .4 currency units .
• The counter value is accumulated till it reaches 999 .9 (the counter does not roll over) .
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time) .
• Local energy price is set with parameter 4502 ENERGY PRICE .
0177
SAVED AMOUNT 2
Energy saved in local currency in thousand currency units . Eg value 5 means 5000 currency units . See the note on page 1-163 .
• The counter value is accumulated till it reaches 65535 (the counter does not roll over) .
• See parameter 0176 SAVED AMOUNT 1 .
0178
SAVED CO
2
Reduction of carbon dioxide emissions in tons . See the note on page 1-163 .
• The counter value is accumulated till it reaches 6553 .5 (the counter does not roll over) .
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time) .
• CO
conversion factor is set with parameter 4507 CO
2
OM 1191 • MD5 VFD
CONV FACTOR .
2
16
P
araMeTers
Par . 3501
= 1...3:
-10...200 °C
Par . 3501 =
1
4: 0...5000
ohm Par .
3501 =
5...6: 0...1
-20 .0...
1 .0 °C
150 .0 °C
0 .0...100 .0%
0 .1%
-32768...
1
+32767
-32768...
1
+32767
0 .0...999 .9
0 .1 kWh
kWh
0...65535
1 MWh
MWh
0 .0...999 .9
0 .1
0...65535
1
0 .0...6553 .5
0 .1 tn
tn
www .DaikinApplied .com