Group 36: Timed Functions

This group defines the timed functions. The timed functions include:
• Four daily start and stop times
• Four weekly start, stop and boost times
• Four timers for collecting selected periods together .
A timer can be connected to multiple time periods and a time period can be in multiple timers .
A parameter can be connected to only one timer . .
You can use the Timed functions assistant for easy configuring.
Table 19: Group 36: Timed Functions
Code
Description
3601
TIMERS ENABLE
Selects the source for the timer enable signal .
0 = NOT SEL – Timed functions are disabled .
1 = DI1 – Defines digital input DI1 as the timed function enable signal.
• The digital input must be activated to enable the timed function .
2...6 = DI2...DI6 – Defines digital input DI2...DI6 as the timed function enable signal.
7 = ACTIVE – Timed functions are enabled .
-1 = DI1(INV) – Defines an inverted digital input DI1 as the timed function enable signal.
• This digital input must be de-activated to enable the timed function .
• -2...-6 = DI2(INV)...DI6(INV) – Defines an inverted digital input DI2...DI6 as the timed function enable signal.
3602
START TIME 1
Defines the daily start time.
• The time can be changed in steps of 2 seconds .
• If parameter value is 07:00:00, the timer is activated at 7 a .m .
• The figure shows multiple timers on different weekdays.
OM 1191 • MD5 VFD
Range
-6...7
00:00:00...23:59:58
36
P
araMeTers
Resolution
Default
S
1
0 (NOT SEL)
2 s
12:00:00 AM
www .DaikinApplied .com