Analog Output Control

Using the fieldbus for analog output control requires:
• Drive parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the
appropriate location. (The location is defined by the
Protocol Reference, which is protocol dependent .)
Table 30: Analog Output Control Parameters
Drive Parameter
1501
AO1 CONTENT SEL
0135
COMM VALUE 1
1507
AO2 CONTENT SEL
0136
COMM VALUE 2

PID Control Setpoint Source

Use the following settings to select the fieldbus as the setpoint source for PID loops:
Table 31: PID Control Setpoint Parameters
Drive Parameter
SET POINT SEL
4010
(Set 1)
8 (COMM VALUE 1)
SET POINT SEL
4110
9 (COMM + AI1)
(Set 2)
10 (COMM*AI1)
SET POINT SEL
4210
(Ext/Trim)

Communication Fault

When using fieldbus control, specify the drive's action if serial communication is lost.
Table 32: Communication Fault Parameters
Drive Parameter
3018
COMM FAULT FUNC
3019
COMM FAULT TIME
www .DaikinApplied .com
Value
Setting
135 (COMM
Analog Output
VALUE 1)
1 controlled
by writing to
parameter 0135 .
136 (COMM
Analog Output
VALUE 2)
2 controlled
by writing to
parameter 0136 .
Value
Setting
Setpoint is either:
• Input Reference
2 (+/-/* AI1) .
Control requires
parameter 1106
value = comm .
• Process PID
setpoint . Control
requires parameter
1106 value = pid1
out and parameter
4010 value =
comm .
0 (NOT SEL)
1 (FAULT)
2 (CONST SP7)
3 (LAST SPEED)
Protocol Reference
Modbus
Daikin DRV
DCU PROFILE
40135
40136
Modbus
Daikin DRV
DCU PROFILE
40003
Value
Set time delay before acting on a communication loss .
53
e
Mbedded
N2
FLN
AO14
46
AO15
47
Protocol Reference
N2
FLN
AO2
61
Description
Set for appropriate drive response .
OM 1191 • MD5 VFD
f
ieldbUs
BACnet
AO0
AO1
BACnet
AV17