Group 37: User Load Curve

This new group defines supervision of user adjustable load curves (motor torque as a function of frequency). The
curve is defined by five points. - The function replaces deleted underload parameters 3013...3015
Table 42: Group 37: User Load Curve
Code
Description
3701
USER LOAD C MODE
Supervision mode for the user adjustable load curves . This functionality replaces the former underload
supervision in Group 30: FAULT FUNCTIONS .
0 = NOT SEL – Supervision is not active .
1 = UNDERLOAD – Supervision for the torque dropping below the underload curve .
2 = OVERLOAD – Supervision for the torque exceeding the overload curve .
3 = BOTH – Supervision for the torque dropping below the underload curve or exceeding the overload curve .
3702
USER LOAD C FUNC
Action wanted during load supervision .
1 = FAULT – A fault is generated when the condition defined by 3701 USER LOAD C MODE has been valid longer than the time set by
3703 USER LOAD C TIME .
2 = ALARM – An alarm is generated when the condition defined by 3701 USER LOAD C MODE has been valid longer than half of the time
defined by 3703 USER LOAD C TIME.
3703
USER LOAD C TIME
Defines the time limit for generating a fault. Half of this time is used as the limit for generating an alarm.
3704
LOAD FREQ 1
Defines the frequency value of the first curve definition point. Must be smaller than 3707 LOAD FREQ 2.
3705
LOAD TORQ LOW 1
Defines the torque value of the first underload curve definition point. Must be smaller than 3706 LOAD TORQ HIGH 1.
3706
LOAD TORQ HIGH 1
Defines the torque value of the first overload curve definition point.
3707
LOAD FREQ 2
Defines the frequency value of the second curve definition point. Must be smaller than 3710 LOAD FREQ 3.
3708
LOAD TORQ LOW 2
Defines the torque value of the second underload curve definition point. Must be smaller than 3709 LOAD TORQ HIGH 2.
3709
LOAD TORQ HIGH 2
Defines the torque value of the second overload curve definition point.
3710
LOAD FREQ 3
Defines the frequency value of the third load curve definition point.
3711
LOAD TORQ LOW 3
Defines the torque value of the third underload curve definition point. Must be smaller than 3712 LOAD TORQ HIGH 3.
3712
LOAD TORQ HIGH 3
Defines the torque value of the third overload curve definition point.
3713
LOAD FREQ 4
Defines the frequency value of the fourth load curve definition point.
3714
LOAD TORQ LOW 4
Defines the torque value of the fourth underload curve definition point. Must be smaller than 3715 LOAD TORQ HIGH 4.
3715
LOAD TORQ HIGH 4
Defines the torque overvalue of the fourth load curve definition point.
3716
LOAD FREQ 5
Defines the frequency value of fifth load curve definition point.
3717
LOAD TORQ LOW 5
Defines the torque value of the fifth underload curve definition point. Must be smaller than 3718 LOAD TORQ HIGH 5.
3718
LOAD TORQ HIGH 5
Defines the torque value of the fifth overload curve definition point.
www .DaikinApplied .com
61
a
s
p
CTual
Ignals and
arameTers
Range
Resolution
Default
0 . . .3
1
0
1, 2
1
1
20 s
5 Hz
10%
300%
25%
15%
300%
43 Hz
25%
300%
50 Hz
30%
300%
500 Hz
30%
300%
OM 1190-1 • MD4 VFD