When the thermal difference is 0°F
• When Representative suction temperature – Representative setpoint (Heat) > Thermal difference + 3,
operation mode is changed from Heat to Cool
• When Representative setpoint (Cool) – Representative suction temperature > Thermal difference + 3,
operation mode is changed from Cool to Heat
Representative setpoint (Heat) +
Thermal difference in (0°F) + 3
Representative setpoint (Cool/Heat)
Representative setpoint (Cool) –
Thermal difference in (0°F) – 3
The following describes how to create and set up an Auto Changeover group.

Creating and editing an Auto Changeover group

1. Touch the Auto Changeover button on the Automatic Ctrl. tab of the Menu List screen and
display the Automatic Changeover settings screen (see page 52).
(1)
is a list of registered Auto Changeover groups. To create a new group, touch the Create
2.
(2)
button
and enter the group name in the Name Setup dialog that appears. Duplicate names
are not permitted. You can create up to 512 groups.
101
Heating mode
Cooling mode
°F
Representative
suction
temperature
Cooling mode
Heating mode
<When the thermal difference is 0°F>
(1)
User's Manual EM11A017
DCM601A71 intelligent Touch Manager
Heating mode
Cooling mode
Heating mode
(2)
(3)
(4)
6°F
3°F
3°F