Interface to the SIMATIC controller
7.4 Setting the "IID_HW_CONNECT" data type
Follow the steps below to read out the parameter values "HW_ID" and "LADDR" for a
channel:
1. Open the device view.
2. Double-click on the reader.
The properties window of the reader opens.
3. In the "RFID communication" > "I/O addresses" tab, and you will find the I/O address that
corresponds to "LADDR".
Note that the input and output address must have the same value.
4. In the "RFID communication" > "Hardware identifier" tab you will find the hardware
identifier that corresponds to the "HW_ID".
Figure 7-3
5. Transfer the values of "LADDR" and "HW_ID" to the PLC data type "IID_HW_CONNECT"
of the reader for which you want to set parameters.
The "IID_HW_CONNECT" data type has now been created and addressed for a channel.
Repeat these steps for every other reader/channel. If you want to use a different channel of
98
The "Hardware identifier" parameter
SIMATIC RF650R/RF680R/RF685R
Configuration Manual, 10/2015, C79000-G8976-C386-03