Interface to the SIMATIC controller
7.7 Programming the Ident profile
Figure 7-20
Sequence of the repeat command without command transfer:
This sequence is only possible if the command involved has already been transferred.
1. Set the "RPTCMD" input parameter.
The Repeat command is activated on the reader.
2. The reader confirms activation with the output parameter "RPTACT" to the Ident profile.
The confirmation is made only after the first command has been executed.
If the reader does not support the Repeat command, "RPTACT" remains inactive. If
"EXECUTE" is nevertheless set, the error "E7FE0900h" is output after a timeout of 10
seconds.
3. You can read out the individual results by setting the "EXECUTE" input parameter several
times.
Figure 7-21
134
Sequence of the repeat command with simultaneous command transfer
Sequence of the repeat command without command transfer
Configuration Manual, 10/2015, C79000-G8976-C386-03
SIMATIC RF650R/RF680R/RF685R