Degraded Mode Link E3G110 Option; Key Data - Siemens AlgoRex CS1140 Planning

Fire detection system
Hide thumbs Also See for AlgoRex CS1140:
Table of Contents

Advertisement

Extinguishing
32.2

Degraded mode link E3G110 option

CPU
E3X10.
or
E3G080
B3Q...
K1
K1
24/5V
B3Q440
32.3

Key data

'Delayed' area valve
'Non-delayed' main valve
(activation of pneumatic path)
Alarm horn
Illuminated panel
Manual activation
Automatic activation
Stop/block button
'Loss of extinguishing agent' reporting contact
'Extinguishing blocked' reporting contact
'Extinguishing activated' reporting contact
Local operating unit
Fire control
Special feature
88
Building Technologies
Fire Safety & Security Products
Allows extinguishing to be activated automatically even if the main CPU fails.
Depends on 2 detectors.
The detectors in the extinguishing SECTION must be split over 2 independent
detector lines.
I-Bus
E3G110
K1
ST1
ST8
1......4
Manual activation
DM1103
Note:
'ST10' connector only provided for E3M060 (MS9i), E3M071 (interactive), E3M171 (interactive Ex),
E3M080 (collective) and E3M111 (AnalogPLUS)
'MIMIC DISPLAY' connector for E3M141
Activation delay of 0..240 s
Limitation of activation period of 0..240 s or until reset
Monitored line
Line can be adjusted to area valve
Limitation of activation period of 0..240 s
Monitored line
Line can be adjusted to main valve
Can be turned off by extinguishing operating unit or control panel
Monitored line
Activation mode active continuously/can be programmed to pulse
Can be shut down separately or remains active until reset
Monitored line
Activation mode active continuously/can be programmed to pulse
Directly only E3G080
Also functions when control panel is in 'degraded mode'
Line monitored
Via detector –> control panel, parameters can be set for alarm, either for:
Detectors in same OBJECT
Detectors in different OBJECTS
Detectors in same or different OBJECTS
All detector models can be used (interactive / AnalogPLUS / collective)
Separate monitored line
Separate monitored line
Separate monitored line
Separate monitored line
Using 'Extinguishing' operating unit B3Q440
Usage recommended, but not compulsory
Max. 4 operating units possible
Via LON data bus with monitored line
Length of line up to 600 m
Via control panel control output
Autonomously functioning I bus component
Integrated degraded mode function
Parameter settings via AlgoWorks
User functions saved on E3G080
Several extinguishing SECTIONS can be interlocked with one another
Automatic adjustment function
CC11, CI11
E3M071
E3M071
ST10 K1
ST10 K1
interactive
detectors
Z1I030/050
E3G110
008725_h_en_--
06.2011