Extinguishing
32.2
Degraded mode link E3G110 option
CPU
E3X10.
or
E3G080
B3Q...
K1
K1
24/5V
B3Q440
32.3
Key data
'Delayed' area valve
'Non-delayed' main valve
(activation of pneumatic path)
Alarm horn
Illuminated panel
Manual activation
Automatic activation
Stop/block button
'Loss of extinguishing agent' reporting contact
'Extinguishing blocked' reporting contact
'Extinguishing activated' reporting contact
Local operating unit
Fire control
Special feature
88
Building Technologies
Fire Safety & Security Products
Allows extinguishing to be activated automatically even if the main CPU fails.
Depends on 2 detectors.
The detectors in the extinguishing SECTION must be split over 2 independent
detector lines.
I-Bus
E3G110
K1
ST1
ST8
1......4
Manual activation
DM1103
Note:
'ST10' connector only provided for E3M060 (MS9i), E3M071 (interactive), E3M171 (interactive Ex),
E3M080 (collective) and E3M111 (AnalogPLUS)
'MIMIC DISPLAY' connector for E3M141
Activation delay of 0..240 s
–
–
Limitation of activation period of 0..240 s or until reset
Monitored line
–
Line can be adjusted to area valve
–
Limitation of activation period of 0..240 s
–
Monitored line
–
–
Line can be adjusted to main valve
Can be turned off by extinguishing operating unit or control panel
–
–
Monitored line
Activation mode active continuously/can be programmed to pulse
–
–
Can be shut down separately or remains active until reset
Monitored line
–
Activation mode active continuously/can be programmed to pulse
–
Directly only E3G080
–
Also functions when control panel is in 'degraded mode'
–
–
Line monitored
Via detector –> control panel, parameters can be set for alarm, either for:
–
–
Detectors in same OBJECT
Detectors in different OBJECTS
–
Detectors in same or different OBJECTS
–
–
All detector models can be used (interactive / AnalogPLUS / collective)
Separate monitored line
–
Separate monitored line
–
Separate monitored line
–
–
Separate monitored line
Using 'Extinguishing' operating unit B3Q440
–
–
Usage recommended, but not compulsory
Max. 4 operating units possible
–
Via LON data bus with monitored line
–
–
Length of line up to 600 m
Via control panel control output
–
Autonomously functioning I bus component
–
Integrated degraded mode function
–
–
Parameter settings via AlgoWorks
User functions saved on E3G080
–
Several extinguishing SECTIONS can be interlocked with one another
–
–
Automatic adjustment function
CC11, CI11
E3M071
E3M071
ST10 K1
ST10 K1
interactive
detectors
Z1I030/050
E3G110
008725_h_en_--
06.2011