HEIDENHAIN iTNC 530 Service Manual page 175

Hide thumbs Also See for iTNC 530:
Table of Contents

Advertisement

Variant
344980-01
344980-02
344980-12
344980-13
344980-14
X31:
Supply voltage: 400 V ± 10 %
Power supply unit
Pin layout:
for UV 105
Connecting terminal
U
V
Power supply of the
The UV 105 is powered with dc-link voltage UZ through
UV 105 with UZ
X69:
When connecting to connector X69/X169 of the CC, see "X69: NC power supply and control
NC supply voltage
signals, see X169" on page 13 – 166
and control signals
May 2006
Changes to UV 105
First edition
Version only for non-HEIDENHAIN inverters
Version only for HEIDENHAIN inverters
Version for HEIDENHAIN and non-HEIDENHAIN
inverters
Leads and ribbon cables elongated for double-row
configuration
a. Connecting cable: 1.5 mm
Note
The supply voltage at terminals U and V must:
be supplied via an isolating transformer (300 VA, basic isolation in accordance with EN 50
178 or VDE 0550) for non-HEIDENHAIN inverters and regenerative HEIDENHAIN inverter
systems.
There is no need for an isolating transformer if non-regenerative HEIDENHAIN inverter
systems are used.
DANGER
Do not ground this isolating transformer on the secondary side!
The isolating transformer decouples the dc-link voltage from ground. Grounding the isolating
transformer on the secondary side leads to an addition of the dc-link voltage and the supply
voltage. This would overload and thus destroy the UV 105.
the conductor bars (for HEIDENHAIN inverter systems).
a cable which is connected instead of the conductor bar (for non-HEIDENHAIN inverter
systems).
Operation with HEIDENHAIN inverters:
For the NC to be able to evaluate the status signals of the compact inverters or the power
supply units, connector X69 must be connected by ribbon cable with X69 of the UV 105.
Operation with non-HEIDENHAIN inverters:
Since status signals from non-HEIDENHAIN inverters are not available or are not
compatible to HEIDENHAIN systems, the adapter (Id. Nr. 349 211-01) must be connected
to X69 on the UV 105.
Assignment
a
U
Va
Equipment ground (YL/GY),
Š 10 mm2
2
13 – 175