One RU has three holes. The holes for one RU are typically marked with a line
below the bottom hole and another line above the top hole. A number at the center
hole identifies where the RU appears in the rack.
Figure 2-1
shows the markings as described.
Rack RU space markings
Figure 2-1
Use the node and the storage shelf Rack Templates to determine the mounting
locations.
Best practices for hardware installation are as follows:
When you install the rails, be sure to use complete RUs. Do not use holes from
different RUs.
The storage shelves are much heavier than the node and should be installed
as close to the bottom of the rack as possible.
The node should always be installed on top of the storage shelves.
Do not leave any spaces between the compute node and a storage shelf, or
between two storage shelves.
When you add expansion shelves to an operational appliance system, turn off
the node(s), the primary shelf, and existing expansion shelves.
To determine rack locations for the hardware
1
Determine the total number of rack units (RUs) that you need as follows:
Pre-installation requirements
Determining rack locations
31