11.7
Details on insulation, protection class, degree of protection and
rated voltage
Insulation
The insulation is designed in compliance with the requirements of IEC 61010-2-201.
NOTE
In the case of I/O devices with 24 V DC (SELV/PELV) supply voltage, galvanic isolations are
tested with 707 V DC (type test).
Pollution class according to IEC 61010-2-201
• Protection class III
Severity for voltage interruption
The I/O device of the distributed I/O system ET 200eco PN M12-L meet the severity class PS2
for voltage interruption (10 ms).
Pollution degree / overvoltage category according to IEC 61010-2-201
Connected according to the specifications in the "Wiring (Page 60)" section:
• Pollution degree: 3
• Overvoltage category: II
In delivery state, with one or more open connections:
• Pollution degree: 2
• Overvoltage category: II
Degree of protection IP65/67, IP69K
Degree of protection of the ET 200eco PN M12-L distributed I/O system:
IP65/IP67 according to IEC 60529
• 1. Code number IP6x: Dust-proof and complete protection from contact
• 2. Code number: Protection from water
– IPx5: Protected against water jets (nozzle) from any angle
– IPx7: Protected against the effects of temporary immersion in water
Distributed I/O system ET 200eco PN M12-L
System Manual, 11/2023, A5E48753295-AG
11.7 Details on insulation, protection class, degree of protection and rated voltage
Water directed as a jet against the housing from any direction must have no harmful
effects.
Water must not enter in a quantity to cause harmful effects when the enclosure is
temporarily immersed in water under standardized pressure condition and time
conditions.
Technical specifications
105