13) G2-2 DeviceLogix Features
Features
DeviceNet Spec. Supported
Bus Topology
Baud Rates Supported
Duplicate address detection
Error Correction
Address Setting
Termination Resistor
(external)
ADR support
Function Blocks
Connection Types Supported
Timers

14) Factory Default Settings

Unless otherwise requested, all standard G2-2 Series DeviceLogix manifolds ship with specific factory default
settings. Below is a list of the factory default settings:
Description
Node Address
Baud Rate
Input Module Power Jumper
Output Module Power Jumper
Communication Status Override
Network Status Override
Valve Side Output Bytes
Discrete I/O Side - I/O Bytes

15) Technical Support

For technical support, contact your local Numatics distributor. If further information is required,
please call Numatics Inc. at (248) 887-4111 and ask for Technical Support.
Issues relating to network set-up, PLC programming, sequencing, software related functions, etc...
should be handled with the appropriate product vendor.
Information on device files, technical manuals, local distributors, and other Numatics, Inc. products
and support issues can be found on the Numatics, Inc's. WEB site at
G2-2 Series DeviceLogix Quick Start Manual
Designed to DeviceNet Specification Revision 2.0
Straight with restricted drops
125Kbps, 250 Kbps and 500 Kbps and Autobaud
If duplicate address detected on power up, duplicates will not
progress to run mode
Yes, if error detected, sender is requested to repeat the message
Via Software or optional Manual Configuration Module (MCM)
A 121 ohms, 1%, ¼ Watt resistor is required at each end of the
trunk line. Not necessary for stand alone applications.
Auto-Device Replacement is supported when the MCM is
disabled or not present. Program sequences are also saved.
Maximum of 72 function blocks supported
Polled, Cyclic, Change of State (COS) or Combinations
Default of 10 millisecond time base only! Regardless of setting.
+24VDC Node and Inputs pin on the Aux. power connector)
+24VDC Valves and Outputs pin on the Aux. power connector)
5/5 (4/4 for valve outputs & valve output status bits;
Self-Configuring based on the I/O modules installed.
3835054 TDG22DLQS3-0
Subject to change without notice
www.numatics.com/fieldbus
Description
Default Settings
63
Autobaud Enabled
PU
(Input sensor power supplied by
SP
(Output module power supplied by
Enabled
stand alone applications
Enabled
1/1 for network I/O) Bytes
www.numatics.com
1/07
Configured for
Page 14