Section 25
Inverse time characteristics
882
Table 667:
IEC Inverse time characteristics for Line Differential protection
Function
Operating characteristic:
æ
ö
A
ç
÷
=
×
t
k
(
)
ç
÷
P
è
-
ø
I
1
EQUATION1251-SMALL V1 EN-US
I = I
/I
measured
set
IEC Normal Inverse
IEC Very inverse
IEC Inverse
IEC Extremely inverse
IEC Short time inverse
IEC Long time inverse
Programmable characteristic
Operate characteristic:
æ
ö
A
ç
÷
=
+
×
t
B
k
(
)
ç
÷
P
è
-
ø
I
C
EQUATION1370-SMALL V1 EN-US
Reset characteristic:
TR
=
×
t
k
(
)
PR
-
I
CR
EQUATION1253-SMALL V1 EN-US
I = I
/I
measured
set
The parameter setting Characterist1 and 4/Reserved shall not be
used, since this parameter setting is for future use and not
implemented yet.
Table 668:
RI and RD type inverse time characteristics for Line Differential protection
Function
RI type inverse characteristic
1
=
×
t
k
0.236
-
0.339
I
EQUATION1137-SMALL V1 EN-US
I = I
/I
measured
set
RD type logarithmic inverse
characteristic
æ
ö
I
-
ç
×
÷
=
5.8
1.35
In
t
è
ø
k
EQUATION1138-SMALL V1 EN-US
I = I
/I
measured
set
Range or value
k = (0.05-2.00) in steps of
0.01
A=0.14, P=0.02
A=13.5, P=1.0
A=0.14, P=0.02
A=80.0, P=2.0
A=0.05, P=0.04
A=120, P=1.0
k = (0.05-999) in steps of 0.01
A=(0.005-200.000) in steps of
0.001
B=(0.00-20.00) in steps of
0.01
C=(0.1-10.0) in steps of 0.1
P=(0.005-3.000) in steps of
0.001
TR=(0.005-100.000) in steps
of 0.001
CR=(0.1-10.0) in steps of 0.1
PR=(0.005-3.000) in steps of
0.001
Range or value
k = (0.05-2.00) in steps of
0.01
k = (0.05-999) in steps of 0.01
Line differential protection RED650 2.2 IEC
1MRK 505 394-UEN A
Accuracy
IEC 60255-151, ± 5.0%
or ± 40 ms whichever is
greater
Accuracy
IEC 60255-151, ± 5.0%
or ± 40 ms whichever is
greater
Technical manual