ABB RED650 Technical Manual page 622

Hide thumbs Also See for RED650:
Table of Contents

Advertisement

Section 16
Metering
Name
tEnergyOffPls
EAFAccPlsQty
EARAccPlsQty
ERFAccPlsQty
ERRAccPlsQty
Table 436:
ETPMMTR Non group settings (advanced)
Name
EALim
ERLim
EnZeroClamp
LevZeroClampP
LevZeroClampQ
DirEnergyAct
DirEnergyReac
EAFPrestVal
EARPrestVal
ERFPresetVal
ERRPresetVal
616
Values (Range)
Unit
0.100 - 60.000
s
0.001 - 10000.000
MWh
0.001 - 10000.000
MWh
0.001 - 10000.000
MVArh
0.001 - 10000.000
MVArh
Values (Range)
Unit
0.001 -
MWh
10000000000.000
0.001 -
MVArh
10000000000.000
Off
-
On
0.001 - 10000.000
MW
0.001 - 10000.000
MVAr
Forward
-
Reverse
Forward
-
Reverse
0.000 -
MWh
100000000.000
0.000 -
MWh
100000000.000
0.000 -
MVArh
100000000.000
0.000 -
MVArh
100000000.000
Step
Default
0.001
0.500
0.001
100.000
0.001
100.000
0.001
100.000
0.001
100.000
Step
Default
0.001
1000000.000
0.001
1000.000
-
On
0.001
10.000
0.001
10.000
-
Forward
-
Forward
0.001
0.000
0.001
0.000
0.001
0.000
0.001
0.000
1MRK 505 394-UEN A
Description
Energy accumulated pulse OFF time in
secs
Pulse quantity for active forward
accumulated energy value
Pulse quantity for active reverse
accumulated energy value
Pulse quantity for reactive forward
accumulated energy value
Pulse quantity for reactive reverse
accumulated energy value
Description
Active energy limit
Reactive energy limit
Enable of zero point clamping detection
function
Zero point clamping level at active
Power
Zero point clamping level at reactive
Power
Direction of active energy flow Forward/
Reverse
Direction of reactive energy flow
Forward/Reverse
Preset Initial value for forward active
energy
Preset Initial value for reverse active
energy
Preset Initial value for forward reactive
energy
Preset Initial value for reverse reactive
energy
Line differential protection RED650 2.2 IEC
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series

Table of Contents