ABB RED650 Technical Manual page 134

Hide thumbs Also See for RED650:
Table of Contents

Advertisement

Section 7
Impedance protection
128
I
jX
L
1
L
2
I
IEC15000060 V1 EN-US
Figure 49:
Simplified mho characteristic and vector diagram for phase L1-to-
L2 fault
Offset Mho
The characteristic for offset mho is a circle with origin as the center and magnitude
of
as the radius, where
Z
1
set
settings.
The condition for operation at phase-to-phase fault is that the angle β between the
two compensated voltages is greater than or equal to 90° (figure 50). The angle will
be 90° for fault location on the boundary of the circle.
The angle β for L1 to L2 fault can be defined according to equation below.
U
I
L L
1 2
L L
1 2
arg
 
U
I
L L
1 2
L L
1 2
IECEQUATION15008 V2 EN-US
Z
1
U
L L
1 2
set
comp
U
L
1L
2
U
pol
is settable through the resistance and reactance
Z
1
set
Z
1
set
Z
1
set
1MRK 505 394-UEN A
U
I
Z
1
L
1
L
2
L
1
L
2
set
I
IEC15000060-1-en.vsdx
GUID-3E13E6D5-0832-4386-9677-9A40BFF42F8F v2
Line differential protection RED650 2.2 IEC
Technical manual
R
L
1
L
2
(Equation 9)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series