Operation Principle; Terminology Explanation; Status Descriptions - ABB RED650 Technical Manual

Hide thumbs Also See for RED650:
Table of Contents

Advertisement

Section 12
Control
Name
ZoneSeqCoord
tSuccessful
tSlaveDeadTime
12.2.6
12.2.6.1
12.2.6.2
326
Values (Range)
Unit
Off
-
On
0.000 - 60.000
s
0.100 - 60.000
s

Operation principle

Terminology explanation

Before describing the auto reclosing function it is first necessary to define the
following terminology:
a shot is an attempt from the function to close a circuit breaker
multi-shot is where more than one shot is attempted
dead time is the time between a start of the function and the attempt to close
the circuit breaker
reclaim time is the time from the circuit breaker closing command till the
reset of the function, should the auto reclosing attempt be successful and no
new start is received
high-speed shot is generally used for an application where the dead time is
less than 1 second and synchrocheck is not required
delayed auto reclosing is generally regarded as an application where the dead
time is greater than 1 second and where typically synchrocheck is required
sequence is the auto reclosing cycle beginning with start and ending with
successful, unsuccessful or aborted reclosing as a result
status is the state which the auto reclosing function have reached in the
sequence

Status descriptions

The auto reclosing function can be in one of the following five statuses:
"Inactive"
The auto recloser is in "inactive" status when the following conditions are fulfilled:
the auto recloser is set to On and
either the circuit breaker is not closed
or the circuit breaker is not ready
The function will not react on any start from protection trips while in
"inactive" status and no automatic reclosing is possible.
Step
Default
-
Off
0.001
1.000
0.001
0.400
1MRK 505 394-UEN A
Description
Coordination of down stream devices to
local protection unit's AR
Delay time before indicating successful
reclosing
Wait time for the slave to close when
WAIT input has reset
GUID-EA0760DF-8F0B-4146-8A42-3F20E75E1053 v1
GUID-AFC069D6-ADA5-4D97-9699-8C9F058458EB v1
GUID-BF80C969-FCBE-4CAB-BF71-9590A2DB433C v1
Line differential protection RED650 2.2 IEC
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series

Table of Contents