Settings - ABB RED650 Technical Manual

Hide thumbs Also See for RED650:
Table of Contents

Advertisement

1MRK 505 394-UEN A
9.1.5
Table 117:
UV2PTUV Group settings (basic)
Name
Values (Range)
Operation
OperationStep1
Characterist1
OpMode1
U1<
t1
t1Min
k1
IntBlkSel1
IntBlkStVal1
tBlkUV1
HystAbs1
OperationStep2
Table continues on next page
Line differential protection RED650 2.2 IEC
Technical manual
Name
START
ST1
ST1L1
ST1L2
ST1L3
ST2
ST2L1
ST2L2
ST2L3

Settings

Unit
Off
-
On
Off
-
On
Definite time
-
Inverse curve A
Inverse curve B
Prog. inv. curve
1 out of 3
-
2 out of 3
3 out of 3
1.0 - 100.0
%UB
0.00 - 6000.00
s
0.000 - 60.000
s
0.05 - 1.10
-
Off
-
Block of trip
Block all
1 - 50
%UB
0.000 - 60.000
s
0.0 - 50.0
%UB
Off
-
On
Type
Description
BOOLEAN
General start signal
BOOLEAN
Common start signal from step1
BOOLEAN
Start signal from step1 phase L1
BOOLEAN
Start signal from step1 phase L2
BOOLEAN
Start signal from step1 phase L3
BOOLEAN
Common start signal from step2
BOOLEAN
Start signal from step2 phase L1
BOOLEAN
Start signal from step2 phase L2
BOOLEAN
Start signal from step2 phase L3
Step
Default
-
Off
-
On
-
Definite time
-
1 out of 3
0.1
70.0
0.01
5.00
0.001
5.000
0.01
0.05
-
Off
1
20
0.001
0.000
0.1
0.5
-
On
Section 9
Voltage protection
Description
Operation Off / On
Enable execution of step 1
Selection of time delay curve type for
step 1
Number of phases required for op (1 of
3, 2 of 3, 3 of 3) from step 1
Voltage setting/start val (DT & IDMT) in
% of UBase, step 1
Definitive time delay of step 1
Minimum operate time for inverse curves
for step 1
Time multiplier for the inverse time delay
for step 1
Internal (low level) blocking mode, step 1
Voltage setting for internal blocking in %
of UBase, step 1
Time delay of internal (low level)
blocking for step 1
Absolute hysteresis in % of UBase, step
1
Enable execution of step 2
PID-3586-SETTINGS v7
229