Section 12
Control
12.2.3
12.2.4
322
Each auto reclosing function can be configured to co-operate with the
synchrocheck function.

Function block

SMBRREC
ON
BLOCKED
OFF
SETON
BLKON
READY
BLKOFF
ACTIVE
RESET
SUCCL
INHIBIT
UNSUCCL
START
INPROGR
STARTHS
1PT1
TRSOTF
2PT1
SKIPHS
3PT1
ZONESTEP
3PT2
TR2P
3PT3
TR3P
3PT4
THOLHOLD
3PT5
CBREADY
PERMIT1P
CBCLOSED
PREP3P
PLCLOST
CLOSECB
SYNC
WFMASTER
WAIT
COUNT1P
RSTCOUNT
COUNT2P
MODEINT
COUNT3P1
COUNT3P2
COUNT3P3
COUNT3P4
COUNT3P5
COUNTAR
MODE
ABORTED
SYNCFAIL
INHIBOUT
IEC06000189-3-en.vsd
IEC06000189 V3 EN-US
Figure 151:
SMBRREC function block

Signals

Table 171:
SMBRREC Input signals
Name
Type
ON
BOOLEAN
OFF
BOOLEAN
BLKON
BOOLEAN
BLKOFF
BOOLEAN
RESET
BOOLEAN
INHIBIT
BOOLEAN
START
BOOLEAN
STARTHS
BOOLEAN
TRSOTF
BOOLEAN
SKIPHS
BOOLEAN
Table continues on next page
Default
Description
0
Switch AR On (at ExternalCtrl = On)
0
Switch AR Off (at ExternalCtrl = On)
0
Set AR in blocked state
0
Release AR from blocked state
0
Reset AR to initial conditions
0
Interrupt and inhibit reclosing sequence
0
Start reclosing sequence
0
Start high-speed reclosing without synchrocheck
0
Continue to shots 2-5 at a trip from switch-on-to-
fault
0
Skip high speed shot and continue with delayed
shots
Line differential protection RED650 2.2 IEC