Functionality; Function Block; Signals; Settings - ABB RED650 Technical Manual

Hide thumbs Also See for RED650:
Table of Contents

Advertisement

Section 18
Station communication
18.4.10.2
18.4.10.3
18.4.10.4
18.4.10.5
Table 475:
GOOSESPRCV Non group settings (basic)
Name
Operation
654

Functionality

GOOSESPRCV is used to receive a single point value using IEC 61850 protocol
via GOOSE.

Function block

GOOSESPRCV
BLOCK
^SRCSPOUT
COMMVALID
IEC10000248-2-en.vsd
IEC10000248 V2 EN-US
Figure 323:
GOOSESPRCV function block

Signals

Except for the BLOCK input, the rest of the inputs of this GOOSE
function block are used for GOOSE connections. These
connections are visible and possible to make only if Easy GOOSE
engineering is enabled. For instructions on how to enable Easy
GOOSE engineering in PCM600, refer to the Engineering Manual.
Table 473:
GOOSESPRCV Input signals
Name
BLOCK
SRCSPOUT
Table 474:
GOOSESPRCV Output signals
Name
SPOUT
DATAVALID
COMMVALID
TEST

Settings

Values (Range)
Unit
Off
-
On
^SPOUT
DATAVALID
TEST
Type
Default
BOOLEAN
0
BOOLEAN
0
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Step
Default
-
Off
1MRK 505 394-UEN A
GUID-0C99A106-C131-45D3-9B81-6B188E35EB34 v3
GUID-A414F31A-323F-4684-BADA-46F9C5E2B0E8 v1
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1
Description
Block of function
Source to single point output
Description
Single point output
Data valid for single point output
Communication valid for single point output
Test output
Description
Operation Off/On
Line differential protection RED650 2.2 IEC
PID-6832-INPUTSIGNALS v3
PID-6832-OUTPUTSIGNALS v3
PID-6832-SETTINGS v3
Technical manual