Section 18
Station communication
18.4.8.4
18.4.8.5
Table 469:
GOOSEINTRCV Non group settings (basic)
Name
Operation
18.4.8.6
650

Signals

Except for the BLOCK input, the rest of the inputs of this GOOSE
function block are used for GOOSE connections. These
connections are visible and possible to make only if Easy GOOSE
engineering is enabled. For instructions on how to enable Easy
GOOSE engineering in PCM600, refer to the Engineering Manual.
Table 467:
GOOSEINTRCV Input signals
Name
BLOCK
SRCINTOUT
Table 468:
GOOSEINTRCV Output signals
Name
INTOUT
DATAVALID
COMMVALID
TEST

Settings

Values (Range)
Unit
Off
-
On

Operation principle

The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not
happen.
The TEST output will go HIGH if the sending IED is in test mode.
Type
Default
Description
BOOLEAN
0
Block of function
INTEGER
0
Source to integer output
Type
Description
INTEGER
Integer output
BOOLEAN
Data valid for integer output
BOOLEAN
Communication valid for integer output
BOOLEAN
Test output
Step
Default
-
Off
1MRK 505 394-UEN A
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1
PID-6829-INPUTSIGNALS v3
PID-6829-OUTPUTSIGNALS v3
Description
Operation Off/On
GUID-5BBDF772-3B3E-4F7C-ABE9-18CE3C1A2E2D v4
Line differential protection RED650 2.2 IEC
Technical manual
PID-6829-SETTINGS v3