1MRK 505 394-UEN A
22.2.2.3
22.2.3
22.2.3.1
Line differential protection RED650 2.2 IEC
Technical manual
Technical data
Table 614:
SFP - Optical ethernet port
Quantity
Number of channels
Standard
Type of fiber
Wave length
Optical connector
Communication speed
Table 615:
SFP - Galvanic RJ45
Quantity
Rated value
Number of
Up to 6 single or 3 redundant or a combination of single and redundant links for
channels
communication using any protocol
Standard
IEEE 802.3u 100BASE-TX
Type of cable
Cat5e FTP
Connector
Type RJ45
Communication
Fast Ethernet 100 Mbit/s
Speed
Table 616:
NUM: Communication ports
NUM
Ethernet connection type
Carrier modules supported
Power supply module (PSM)
Introduction
The power supply module is used to provide the correct internal voltages and full
isolation between the IED and the battery system. An internal fail alarm output is
available.
Alternative connectors of Ring lug or Compression type can be ordered.
IED hardware
Rated value
4 single or 2 redundant can be used for single or
redundant communication using any protocol
IEEE 802.3u 100BASE-FX
62.5/125 mm multimode fibre
1310 nm, Class 1 laser safety
Type LC
Fast Ethernet 100 Mbit/s
GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v2
4 Ethernet ports
1 Basic, 3 Optional
SFP Optical LC or Galvanic RJ45
LDCM
Section 22
SEMOD55319-1 v1
SEMOD55310-2 v11
IP15594-1 v1
M11595-3 v6
813