ABB RED650 Technical Manual page 59

Hide thumbs Also See for RED650:
Table of Contents

Advertisement

1MRK 505 394-UEN A
Table 10:
TRM_7I_5U Non group settings (basic)
Name
Values (Range)
CTStarPoint1
CTsec1
CTprim1
CTStarPoint2
CTsec2
CTprim2
CTStarPoint3
CTsec3
CTprim3
CTStarPoint4
CTsec4
CTprim4
CTStarPoint5
CTsec5
CTprim5
CTStarPoint6
CTsec6
CTprim6
CTStarPoint7
CTsec7
CTprim7
VTsec8
VTprim8
VTsec9
VTprim9
VTsec10
VTprim10
VTsec11
VTprim11
VTsec12
VTprim12
Line differential protection RED650 2.2 IEC
Technical manual
Unit
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
0.001 - 999.999
V
0.05 - 2000.00
kV
0.001 - 999.999
V
0.05 - 2000.00
kV
0.001 - 999.999
V
0.05 - 2000.00
kV
0.001 - 999.999
V
0.05 - 2000.00
kV
0.001 - 999.999
V
0.05 - 2000.00
kV
Step
Default
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
0.001
110.000
0.05
400.00
0.001
110.000
0.05
400.00
0.001
110.000
0.05
400.00
0.001
110.000
0.05
400.00
0.001
110.000
0.05
400.00
Section 3
Analog inputs
Description
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
Rated VT secondary voltage
Rated VT primary voltage
Rated VT secondary voltage
Rated VT primary voltage
Rated VT secondary voltage
Rated VT primary voltage
Rated VT secondary voltage
Rated VT primary voltage
Rated VT secondary voltage
Rated VT primary voltage
PID-3923-SETTINGS v7
53

Hide quick links: