Technical Data; Logic For Group Alarm Almcalh; Identification - ABB RED650 Technical Manual

Hide thumbs Also See for RED650:
Table of Contents

Advertisement

Section 14
Logic
14.3.7
14.4
14.4.1
452
ModeOutput1=Pulsed
INPUT 1
³1
ModeOutput2=Pulsed
INPUT 17
³1
ModeOutput3=Pulsed
IEC09000612 V3 EN-US
Figure 228:
Trip matrix internal logic
Output signals from TMAGAPC are typically connected to other logic blocks or
directly to output contacts in the IED. When used for direct tripping of the circuit
breaker(s) the pulse time shall be set to at least 0.150 seconds in order to obtain
satisfactory minimum duration of the trip pulse to the circuit breaker trip coils.

Technical data

Table 260:
Number of TMAGAPC instances
Function
3 ms
TMAGAPC
6

Logic for group alarm ALMCALH

Identification

Function description
Logic for group alarm
Ondelay
t
Ondelay
t
Ondelay
³1
t
Quantity with cycle time
8 ms
6
IEC 61850
identification
ALMCALH
Line differential protection RED650 2.2 IEC
1MRK 505 394-UEN A
PulseTime
t
&
³1
Offdelay
&
t
PulseTime
t
&
³1
Offdelay
&
t
PulseTime
t
&
³1
Offdelay
&
t
IEC09000612-3-en.vsd
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v1
100 ms
-
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Technical manual
OUTPUT 1
OUTPUT 2
OUTPUT 3