Settings; Technical Data; Exclusive Or Function Block Xor; Function Block - ABB RED650 Technical Manual

Hide thumbs Also See for RED650:
Table of Contents

Advertisement

Section 14
Logic
14.7.9.3
Table 305:
TIMERSET Group settings (basic)
Name
Operation
t
14.7.9.4
14.7.10
14.7.10.1
470

Settings

Values (Range)
Unit
Off
-
On
0.000 - 90000.000
s

Technical data

Table 306:
Number of TIMERSET instances
Logic block
TIMERSET

Exclusive OR function block XOR

The exclusive OR function (XOR) is used to generate combinatory expressions
with boolean variables. XOR has two inputs and two outputs. One of the outputs is
inverted. The output signal OUT is 1 if the input signals are different and 0 if they
are the same.
Table 307:
Truth table for XOR function block
INPUT1
INPUT2
0
0
0
1
1
0
1
1

Function block

XOR
INPUT1
INPUT2
IEC04000409-2-en.vsd
IEC04000409 V2 EN-US
Figure 240:
XOR function block
Step
Default
-
Off
0.001
0.000
Quantity with cycle time
Range or Value
3 ms
8 ms
100 ms
15
15
30
(0.000–90000.000) s
OUT
NOUT
0
1
1
0
1
0
0
1
OUT
NOUT
1MRK 505 394-UEN A
Description
Operation Off/On
Delay for settable timer n
GUID-C6C98FE0-F559-45EE-B853-464516775417 v2
Accuracy
±0.5% ±10 ms
Line differential protection RED650 2.2 IEC
Technical manual
PID-6976-SETTINGS v1
IP11018-1 v2
M11477-3 v4
M11476-3 v1