ABB RED650 Technical Manual page 584

Hide thumbs Also See for RED650:
Table of Contents

Advertisement

Section 15
Monitoring
578
Analog signals
Binary signals
IEC09000336 V3 EN-US
Figure 284:
Disturbance report functions and related function blocks
The whole disturbance report can contain information for a number of recordings,
each with the data coming from all the parts mentioned above. The event list
function is working continuously, independent of disturbance triggering, recording
time, and so on. Settings information function contains all the visible settings,
parameter information of components configured in ACT, runtime status and
IEC61850 behavior that is added to the disturbance record header file. These
settings information is recorded in XML format and then grouped for each function
instance in the HDR file. The function, setting names and Enum values are same as
in the HMI and can be translated to the selected HMI language. All setting values
are updated along with the units. If the setting values are related to the global base
value, then the setting value is scaled and updated with corresponding global base
unit. All information in the disturbance report is stored in non-volatile flash
memories. This implies that no information is lost in case of loss of auxiliary
power. Each report will get an identification number in the interval from 0-999.
AxRADR
DRPRDRE
Trip value rec
Disturbance
BxRBDR
recorder
Event list
Event recorder
Indications
Line differential protection RED650 2.2 IEC
1MRK 505 394-UEN A
Disturbance Report
FL
Fault locator
IEC09000336-3-en.vsdx
Technical manual