Basic IED functions
790
More than one input may be activated at the same time. In such cases the lower
order setting group has priority. This means that if for example both group four and
group two are set to be activated, group two will be the one activated.
Every time a setting is changed, the output signal SETCHGD is sending a pulse.
Activating or deactivating test mode is made by changing a parameter,
consequently this will also cause a pulse on the SETCHGD output.
The parameter MaxNoSetGrp defines the maximum number of setting groups in
use to switch between.
The output REMSETEN indicates whether setting changes over IEC 61850 are
enabled or not. Per default, this is not enabled, which results in REMSETEN being
at a logical low level. If setting changes via IEC 61850 are enabled, then
REMSETEN will be a logical high. The setting changes over IEC 61850 is enabled
with the setting EnableSettings in the IEC 61850-8-1 configuration under Main
menu/Configuration/Communication/Station communication/IEC
61850-8-1/IEC 61850-8-1. Please refer to documentation for IEC 61850 for further
details.
Switching can only be done within that number of groups. The number of setting
groups selected to be used will be filtered so only the setting groups used will be
shown on the Parameter Setting Tool.
+RL2
IEC05000119 V3 EN-US
Figure 365:
Connection of the function to external circuits
The above example also includes seven output signals, for confirmation of which
group that is active.
ACTIVATE GROUP 6
ACTIVATE GROUP 5
ACTIVATE GROUP 4
ACTIVATE GROUP 3
ACTIVATE GROUP 2
ACTIVATE GROUP 1
IOx-Bly1
Æ
IOx-Bly2
Æ
IOx-Bly3
Æ
IOx-Bly4
Æ
IOx-Bly5
Æ
IOx-Bly6
Æ
Line differential protection RED650 2.2 IEC
1MRK 505 394-UEN A
ACTVGRP
ACTGRP1
GRP1
ACTGRP2
GRP2
ACTGRP3
GRP3
ACTGRP4
GRP4
ACTGRP5
GRP5
ACTGRP6
GRP6
SETCHGD
REMSETEN
IEC05000119-3-en.vsd