ABB RED650 Technical Manual page 336

Hide thumbs Also See for RED650:
Table of Contents

Advertisement

Section 12
Control
330
Operation
AND
ExternalCtrl
AND
ON
AND
OFF
StartByCBOpen
AND
START
AND
STARTHS
AND
AND
TRSOTF
startThermal
CBReady
120ms
CBREADY
t
AND
tCBClosedMin
CBCLOSED
t
cbClosed
AND
inhibit
OR
INHIBIT
IEC16000153 V1 EN-US
Figure 152:
Simplified logic for Operation Off/On and starting
Mode selection
The auto reclosing mode is selected with the setting ARMode. As an alternative to
the setting, the mode can be selected by connecting an integer, for example from
function block B16I, to the MODEINT input. The six possible modes are described
in Table
176
below with their corresponding MODEINT integer value.
When a valid integer is connected to the input MODEINT the selected setting
ARMode will be invalid and the MODEINT input value will be used instead. The
selected mode is reported as an integer on the MODE output.
Please note that tripping mode of the IED is defined in Trip Logic function block
SMPPTRC. For example for two-phase faults either 2ph or 3ph tripping and
consequent auto reclosing can be selected
S
OR
R
OR
OR
100ms
100ms
AND
OR
AND
S
AND
R
count0
Line differential protection RED650 2.2 IEC
1MRK 505 394-UEN A
SETON
initiate
OR
start
READY
AND
IEC16000153-1-en.vsdx
GUID-25A24DC8-80C8-4C42-A084-D25712049F06 v1
Technical manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series

Table of Contents