Section 3
Analog inputs
Table 11:
TRM_9I_3U Non group settings (basic)
Name
CTStarPoint1
CTsec1
CTprim1
CTStarPoint2
CTsec2
CTprim2
CTStarPoint3
CTsec3
CTprim3
CTStarPoint4
CTsec4
CTprim4
CTStarPoint5
CTsec5
CTprim5
CTStarPoint6
CTsec6
CTprim6
CTStarPoint7
CTsec7
CTprim7
CTStarPoint8
CTsec8
CTprim8
CTStarPoint9
CTsec9
CTprim9
VTsec10
VTprim10
VTsec11
Table continues on next page
54
Values (Range)
Unit
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
FromObject
-
ToObject
1 - 10
A
1 - 99999
A
0.001 - 999.999
V
0.05 - 2000.00
kV
0.001 - 999.999
V
Step
Default
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
-
ToObject
1
1
1
3000
0.001
110.000
0.05
400.00
0.001
110.000
1MRK 505 394-UEN A
Description
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
ToObject= towards protected object,
FromObject= the opposite
Rated CT secondary current
Rated CT primary current
Rated VT secondary voltage
Rated VT primary voltage
Rated VT secondary voltage
Line differential protection RED650 2.2 IEC
Technical manual
PID-3924-SETTINGS v7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 650 series

Table of Contents