Section 15
Monitoring
Name
OperNoFault
tTrOpenAlm
tTrCloseAlm
OperAlmLevel
OperLOLevel
AccSelCal
CurrExponent
AccStopCurr
AlmAccCurrPwr
LOAccCurrPwr
SpChAlmTime
InitCBRemLife
InactiveAlDays
Table 390:
SSCBR Non group settings (advanced)
Name
OpenTimeCorr
CloseTimeCorr
DirCoef
CBLifeAlmLevel
ContTrCorr
OperTimeDelay
tDGasPresAlm
tDGasPresLO
InitCounterVal
InitAccCurrPwr
InitInactDays
InactiveAlHrs
542
Values (Range)
Unit
1 - 10000
-
0.000 - 0.200
s
0.000 - 0.200
s
0 - 9999
-
0 - 9999
-
Aux Contact
-
Trip Signal
0.50 - 3.00
-
5.00 - 100.00
%IB
0.00 - 20000.00
-
0.00 - 20000.00
-
0.00 - 60.00
s
1 - 99999
-
0 - 9999
Day
Values (Range)
Unit
-0.100 - 0.100
s
-0.100 - 0.100
s
-3.00 - -0.50
-
1 - 99999
-
-0.010 - 0.010
s
0.000 - 0.200
s
0.00 - 60.00
s
0.00 - 60.00
s
0 - 9999
-
0.00 - 9999.99
-
0 - 9999
Day
0 - 23
Hour
Step
Default
1
1000
0.001
0.040
0.001
0.040
1
200
1
300
-
Trip Signal
0.01
2.00
0.01
10.00
0.01
2500.00
0.01
2500.00
0.01
1.00
1
10000
1
2000
Step
Default
0.001
0.010
0.001
0.010
0.01
-1.50
1
5000
0.001
0.005
0.001
0.020
0.01
0.10
0.01
0.10
1
0
0.01
0.00
1
0
1
0
1MRK 505 394-UEN A
Description
Number of operations possible at rated
fault current
Alarm level for open travel time
Alarm level for close travel time
Alarm level for number of operations
Lockout level for number of operations
Accumulated energy calculation
selection
Current exponent value used for energy
calculation
RMS current level below which energy
accumulation stops
Alarm level for accumulated
I^CurrExponent integrated over CB open
travel time
Lockout level for accumulated
I^CurrExponent integrated over CB open
travel time
Alarm level for spring charging time
Initial value for remaining life estimates
Alarm level for inactive days counter
Description
Correction for open travel time
Correction for close travel time
Directional coefficient for CB life
calculation
Alarm level for CB remaining life
Correction for time difference in auxiliary
and main contacts open time
Time delay between change of status of
trip output and start of main contact
separation
Time delay for gas pressure alarm
Time delay for gas pressure lockout
Initial value for number of operations
Initial value for accum I^CurrExponent
integr over CB open travel time value
Initial value for inactive days
Alarm time for inactive days counter in
hours
Line differential protection RED650 2.2 IEC
Technical manual