Section 7
Impedance protection
7.3.5
Table 57:
ZCVPSOF Group settings (basic)
Name
Operation
AutoInitMode
Mode
IPh<
UPh<
tDuration
tSOTF
tDLD
tOperate
Table 58:
ZCVPSOF Non group settings (basic)
Name
GlobalBaseSel
7.3.6
156
Table 56:
ZCVPSOF Output signals
Name
TRIP

Settings

Values (Range)
Unit
Off
-
On
DLD disabled
-
Voltage
Current
Current & Voltage
Impedance
-
UILevel
UILvl&Imp
1 - 100
%IB
1 - 100
%UB
0.000 - 60.000
s
0.000 - 60.000
s
0.000 - 60.000
s
0.03 - 120.00
s
Values (Range)
Unit
1 - 12
-

Monitored data

Table 59:
ZCVPSOF Monitored data
Name
IL1
IL2
IL3
Table continues on next page
Type
Description
BOOLEAN
Trip output
Step
Default
-
Off
-
DLD disabled
-
UILevel
1
20
1
70
0.001
0.020
0.001
1.000
0.001
0.200
0.01
0.03
Step
Default
1
1
Type
Values (Range)
REAL
-
REAL
-
REAL
-
1MRK 505 394-UEN A
PID-3875-OUTPUTSIGNALS v9
Description
Operation Off / On
Automatic switch onto fault initialization
Mode of operation of SOTF Function
Current level for detection of dead line in
% of IBase
Voltage level for detection of dead line in
% of UBase
Time delay for UI detection (s)
Drop off delay time of switch onto fault
function
Delay time for activation of dead line
detection
Time delay to operate of switch onto
fault function
Description
Selection of one of the Global Base
Value groups
PID-3875-MONITOREDDATA v7
Unit
Description
A
Current in phase L1
A
Current in phase L2
A
Current in phase L3
Line differential protection RED650 2.2 IEC
Technical manual
IP15016-1 v2