ABB RED650 Technical Manual page 362

Hide thumbs Also See for RED650:
Table of Contents

Advertisement

Section 12
Control
356
operate from local, station and remote level without any priority. When the external
panel switch is in Off position, the PSTO output shows the actual state of the
switch that is, 0. In this case, it is not possible to control anything. The LocSta
command value is forced to FALSE if AllPSTOValid is set to No priority.
If the setting RemoteIncStation is set to Yes and the LR-switch position is in
Remote state, the PSTO output is set to 2 (Station or Remote), that is, it is
permitted to operate from both station and remote level without any priority.
If the LR-switch position is in Remote state, and AllPSTOValid is set to Priority
and RemoteIncStation is set to No, the switching between station and remote level
control is done through the command LocSta. The command is accessible only
through the IEC 61850 Edition 2 protocol.
Table 189:
PSTO values for different Local panel switch positions
Local panel
AllPSTOValid
switch positions
(setting)
0 = Off
-
1 = Local
Priority
1 = Local
No priority
2 = Remote
Priority
2 = Remote
Priority
2 = Remote
Priority
2 = Remote
No priority
3 = Faulty
-
Blockings
The blocking states for position indications and commands are intended to provide
the possibility for the user to make common blockings for the functions configured
within a complete bay.
The blocking facilities provided by the bay control function are the following:
RemoteInc
LocSta.CtlVal
PSTO
Station
(command)
value
(setting)
-
-
-
-
-
-
No
TRUE
No
FALSE
Yes
-
-
-
-
-
Line differential protection RED650 2.2 IEC
1MRK 505 394-UEN A
LED indications
Possible
on LHMI
locations that
shall be able to
operate
0
Remote and
Not possible
Local Off
to operate
1
Remote Off,
Local Panel
Local On
5
Remote and
Local, Station
Local On
or Remote
level without
any priority
6
Remote On,
Station level
Local Off
7
Remote On,
Remote level
Local Off
2
Remote On,
Station or
Local Off
Remote level
5
Remote and
Local, Station
Local On
or Remote
level without
any priority
3
Remote and
Not possible
Local
to operate
Flashing
Technical manual
M13446-50 v5